Power Automation and Protection Division
I.L. 40-201.9
REL 352 Version 1.00
K-1
K
A
P
P
E
N
D
I
X
APPLICATION NOTES
1.
COMMUNICATION EQUIPMENT INTERFACE
1.1.
REL 352/TCF-10B
NOTE 1:
ALL VOLTAGE SELECTION JUMPERS IN REL 352 AND TCF 10B TO BE SET TO 15/20 V POSITION
NOTE 2:
+20 V ZENER REGULATOR INCLUDED WITH TCF 10B
NOTE 3:
WIRES 2, 11, 12 IN SHIELDED CABLE, CONNECT SHIELD TO TB4-10 OF REL 352
NOTE 4:
WIRES 2, 8, 9, 10 IN SHIELDED CABLE, RUN WIRES 9 AND 10 IN SEPARATE PAIRS, CONNECT SHIELD
TO TB4-10 OF REL 352
Figure 1. REL 352 / TCF-10B Interconnecting Diagram
TCF 10B
REL 352
SHIELD
TB4-10
CHAN FAIL 1 +
SPACE 1 +
MARK 1 +
NOISE
SPACE
MARK
COMM-
+20v
TB1-3
TB1-4
TB1-2
TB1-6
TB1-1
TB5-9
TB5-7
TB5-8
TB5-10
TB4-6
TB4-5
TB4-13
TB4-12
TB4-11
TB4-4
TB4-6
TB4-5
+PWR OFF
-KEY
COMMON
+KEY
XMTR B+
XMTR RTRN -
KEY+
RETURN 1 -
TB7-1
TB7-2
+20 V
TB6-11
(FT1-11)
TB6-12
(FT1-12)
+DC IN
-DC IN
BP
BN
+BATT
NEG
NOTE 2
FAIL
ALARM
(NC CONTACT)
NOTE 3
NOTE 4
5
3
6
7
4
2
8
9
10
11
12