I.L. 40-201.9
Power Automation and Protection Division
2-2
REL 352 Version 1.00
3
CONTACT DATA
Trip Contacts — make & carry 30 A for 1 second, 10 A continuous capability, break 50 watts
resistive or 25 watts with L/R = .045 seconds.
• Non-Trip Contacts
1 A Continuous
0.1 A Resistive Interrupt Capability
Contacts also meet IEC - 255-6A, IEC - 255-12, IEC -255-16, BS142-1982.
4
COMMUNICATION EQUIPMENT INTERFACE
4.1
INPUTS
Optoisolated (7500 V peak) jumper configurable for 20 V, 48 V, 125 V
external dc Power Supply
Operation “On” State Current:
20 V
15 mA
48 V
6 mA
125 V
6 mA
Interfaces to Power Line Carrier (ON-OFF and FSK) Audio Tone and Microwave.
Mark 1
Space 1
Channel Failure 1
Mark 2
Space 2
Channel Failure 2
4.2
OUTPUT
Optoisolated (7500 V peak) Power Transistor Output (Rated 400 V) supporting
external dc
power supply operation in the range of 20 - 150 V dc.
Interfaces to:
Carrier on/off (for ON-OFF PLC) or Carrier mark / space (for FSK PLC) control.
5
OPTIONAL COMPUTER/NETWORK INTERFACE
• RS232C/PONI
— for single point computer communications
• INCOM/PONI
— for local network communications using INCOM network
6
CHASSIS DIMENSIONS AND WEIGHT
Height 7" (177.8 mm) 4 Rack Units (
See Figure 2-1
)
Width 19" (482.6 mm)
Depth 14" (356 mm) including terminal blocks
Weight 38 lb. (17.5 kg)
3 Terminal Application
}