                                                                  Quick Start Guide For The DNP Orion To ABB REL 356 Relays Using Modbus AN-55A-00

13

ORION Troubleshooting Guide

This section illustrates some common solutions to problems encountered when configuring an ORION
unit in the configuration described in this Quick Start Guide.  Reference Table 1 below.

Table 1 – Troubleshooting Guide

ISSUE

RESOLUTION

1. The ORION unit LED’s do not illuminate.

A.

 

Verify the power wiring to the power
connector (Figure 1 Illustration 1).

B.

 

Check for a blown fuse (Figure 1
Illustration 2).

2. The ORION  Green  RUN LED does not
flash
 at a 1 second  interval.

A.

 

Unit is defective.  Contact reseller for a
return authorization number

3. Communication does not occur between the
Diagnostic port and the emulator terminal on
the ORION. (Unit will not attach for
configuration of the unit [Steps 15 through 21]).

A.

 

Verify  the RS 232 Cable Connections from
the PC to ORION Diag port. (Figure 2
Illustration 7).

B.

 

Verify the PC to Prot Conv  settings
accessible through the setup menu of the
CON2MOD setup utility. (Step 10 Figure
4).

C.

 

Does the PC com port match the com port
settings in  the  PC to Prot Conv setting
menu.  (Step 10 Figure 4).

4. The ORION Amber CONFIG LED  flashes.

A.

 

The ORION has not been configured.
Download the saved configuration file from
the configuration terminal. (Step 15 Figure
9)

5. Communication does not occur between the
relay and the ORION connection via the IED
port on the ORION.

A.

 

Verify  the Supplied IED RS 485
connections and cable connections as
shown in  Figure 2.

B.

 

 Verify  the port parameters in the attached
relay as described in Step 7.

C.

 

Verify the ORION configuration settings  as
described in  Step  11 Figure 5.

D.

 

Have the configuration settings been
downloaded to the ORION as described in
Step 15 Figure 9.

E.

 

Modify  the Warm –Up and Warm Down
delays in the Modbus IED port
parameterization screen  to be 10 mS less
than is presently configured.  Download the
new configuration to the ORION Unit. (Step
11 Figure 5 and Step 15 Figure 9).

6. The Red TX or RX LED’s do not illuminate
on the ORION Unit when the DNP 3.0 Host
communicates to the ORION Unit.

A.

 

Verify  the SCADA Port Cabling per the
Host manufacturer’s specification.

B.

 

Verify  the Conitel Port Configuration
through the setup menu of the CON2MOD
setup utility.  (Step 12 Figure 6).

C.

 

Port Timeout has occurred; decrease the
Warm Up and Warm-down timeout values
by 10 mS until issue resolved.

www 

. ElectricalPartManuals 

. com

Summary of Contents for REL 356

Page 1: ...Diskette 1 It is imperative to realize that the ORION is available in two formats a 19 rack mount version and a Table Top version Please refer to the appropriate diagrams when using this guide Apply p...

Page 2: ...st to the ORION SCADA MASTER RS 232 port with a 9 pin D shell connector The cable end should mate with the ORION s male connector The unit is a DTE pinout and a custom cable may have to be developed f...

Page 3: ...hld IED 55 56 57 58 59 60 61 RS 485 AUX COM Isolated Port Shield Bare Wire Relay Pin 55 to Orion Terminal B TX RX Relay Pin 56 to Orion Terminal A TX RX Relay Pin 57 to Orion Terminal Shld Ground Illu...

Page 4: ...tor termination Breakouts of each of the jumper locations are shown in Illustration 1 and Illustration 2 The position of the jumpers in the open or closed positions are highlighted FOR AN ORION TABLE...

Page 5: ...cation through the AUX COM PORT Its location is shown in Figure 2 illustration 6 and Illustration 5 or Illustration 2 depending upon the physical connection type or Figure 2A illustration 5 Connect th...

Page 6: ...uide For The DNP Orion To ABB REL 356 Relays Using Modbus 6 Figure 4 PC Port Menu Selection VI A Comset Figure 5 MODBUS PONI M Configuration Menu Presentation w w w E l e c t r i c a l P a r t M a n u...

Page 7: ...ion RS 485 To Modbus PONI PONI M Port E C NORMAL FAIL PICKUP RECLOSEROUT SYSTEM RESET T I M E INSTANTANEOUS FREQUENCY NEGATIVE SEQUENCE TARGET RESET STATUS T A R G E T S A B C N DPU 2000R Network Part...

Page 8: ...Select the parameters as shown The Port selection however should be modified to match your computer systems hardware configuration After selection of all parameters simultaneously depress the CONTROL...

Page 9: ...select the PROTCONV CONITEL Setup submenu selection until the following screen is displayed The parameters listed in Figure 6 match those in the CONITEL Host After selection of all parameters simultan...

Page 10: ...everal choices is displayed Select the ADD INPUTS selection NovaTech Conitel Modbus Configuration Program PRINTER READY FILE NAME TEST CTL File Setup Memory Map Transfer About 10 37 30 Standard Add In...

Page 11: ...AME TEST CTL File Setup Memory Map Transfer About 10 38 33 Standard Modbus Conitel Input Conitel Data Type AI Point Description Analog Input 1 Conitel Group 1 Conitel Point Start 1 Number of Conitel P...

Page 12: ...US CONITEL OFF ADDR 1 MODBUS OFF 1 TOGGLE CONITEL PORT DISPLAY CURRENTLY OFF 2 TOGGLE MODBUS PORT DISPLAY CURRENTLY OFF M MODEM SETUP and TEST MENU S DISPLAY COMMUNICATION STATISTICS Please enter your...

Page 13: ...menu Step 10 Figure 4 4 The ORION Amber CONFIG LED flashes A The ORION has not been configured Download the saved configuration file from the configuration terminal Step 15 Figure 9 5 Communication d...

Page 14: ...istors are configured in the IED protective relay Jumpers J6 termination J8 Pullup and J7 Pulldown Step 6 9 Communications Strings are not visible when the RUN MMI and submenu 1 Toggle DNP 3 0 Port Di...

Page 15: ...Jumpers J6 termination J8 Pullup and J7 Pulldown Step 6 Optional Information The RS 232 Cables and RS 485 Cable diagrams are included below for reference ORION RS 232 C CABLE Personal Computer OR ORIO...

Page 16: ...ardType 8 Card MODBUS EMULATION COM 3 DB9 Female DB 9 Male to Phoenix Connector Adapter Assembly 1 TX RX 2 TX RX 7 Common REL 356 PONI END UNIT INSTALL TERMINATION RESISTOR 120 OHMS J 15 Closed A B Sh...

Reviews: