ABB REL 356 Current Differential Protection
5-7
Testing
Test Conditions: Case 2 - C0=0, C1=0.1, C2=0.7, OTH=0.50 (OTH=0.70 for V1.15 or lower)
Test Table 2
Fault Type
I
Amps
Ð
Angle
Calculated
Pickup Value
Current
Pickup range
AG
I
A
= 1.56
Ð
0
I
B
= 0
Ð
-120
I
C
= 0
Ð
-240
1.56A
1.31 – 1.81A
BG
I
A
= 0
Ð
0
I
B
= 2.54
Ð
-120
I
C
= 0
Ð
-240
2.54A
2.28 – 2.79A
CG
I
A
= 0
Ð
0
I
B
= 0
Ð
-120
I
C
= 2.54
Ð
-240
2.54A
2.28 – 2.79A
AB
I
A
= 2.20
Ð
0
I
B
= 2.20
Ð
-180
I
C
= 0
Ð
-240
2.20A
1.95 – 2.45A
BC
I
A
= 0
Ð
0
I
B
= 1.80
Ð
-120
I
C
= 1.80
Ð
-300
1.80A
1.55 – 2.05A
CA
I
A
= 2.20
Ð
-60
I
B
= 0
Ð
-120
I
C
= 2.20
Ð
-240
2.20A
1.95 – 2.45A
ABC
I
A
= 8.33
Ð
0
I
B
= 8.33
Ð
-120
I
C
= 8.33
Ð
-240
8.83A
7.50 – 9.16A
Test Conditions: Case 3 - C0=2.5, C1=0.1, C2=0.7, OTH=0.50 (OTH=0.70 for V1.15 or lower)
Test Table 3
Fault Type
I
Amps
Ð
Angle
Calculated
Pickup Value
Current
Pickup range
AG
I
A
= 0.81
Ð
0
I
B
= 0
Ð
-120
I
C
= 0
Ð
-240
0.81A
0.56 – 1.06A
BG
I
A
= 0
Ð
0
I
B
= 1.08
Ð
-120
I
C
= 0
Ð
-240
1.08A
0.83 – 1.33A
CG
I
A
= 0
Ð
0
I
B
= 0
Ð
-120
I
C
= 1.08
Ð
-240
1.08A
0.83 – 1.33A
AB
I
A
= 2.20
Ð
0
I
B
= 2.20
Ð
-180
I
C
= 0
Ð
-240
2.20A
1.95 – 2.45A
BC
I
A
= 0
Ð
0
I
B
= 1.80
Ð
-120
I
C
= 1.80
Ð
-300
1.80A
1.55 – 2.05A
CA
I
A
= 2.20
Ð
-60
I
B
= 0
Ð
-120
I
C
= 2.20
Ð
-240
2.20A
1.95 – 2.45A
ABC
I
A
= 8.33
Ð
0
I
B
= 8.33
Ð
-120
I
C
= 8.33
Ð
-240
8.33A
7.50 – 9.16A
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...