ABB REL 356 Current Differential Protection
5-10
Testing
Functional Tests – Optional Backup System
For units that include the stepped distance backup system the following tests will functionally test all the distance units
provided.
Disconnect the loopback connections as described in step 2 on page 5-3, and make sure the front panel display shows
CHTB as the signal received. A channel trouble enables the optional backup distance system to operate.
The following inital settings should be used:
PANG =
75
GANG =
75
ZR
=
3.0
BKUP =
IN
LOPB =
NO
FDOP =
IN
FDOG =
IN
DIRU
=
ZSEQ
IOM
=
0.5
TOG
=
BLK
Z2P
=
4.5
T2P
=
0.1
Z2GF
=
4.5
Z2GR =
0.01
T2G
=
0.1
Z3P
=
7.0
T3P
=
BLK
Z3GF
=
7.0
Z3GR =
0.01
T3G
=
BLK
Phase to Ground Units
To calculate the fault impedance seen by the relay system the following formula applies:
Where x is either phase a,b, or c.
The above formula is rigorous and general. However, if a quick approximation of the minimum trip current required at
different angles (
q
) is desired, the following formula applies:
Z 2GF*
(PANG -
q) [1 + (ZR - 1)/3]
cos
V
XG
--------------------------------------------------------------------------------------
lxg =
where x is either phase a, b, or c.
Zone 2 Phase-Ground Element Without Reverse Reach
1.
Forward Internal Faults
For forward Zone 2 Phase-Ground Internal Faults use Table 5-1 of voltages and currents. In each case apply the 3-
phase voltage to the relay system first then suddenly apply the currents listed. Compare the relay system trip target
data to the applied fault values. The target data should be /- 10% on magnitude and +/- 3 degrees on phase. Trip
time should fall within 100-132 milliseconds.
Z fault =
Vxg
I
X
g
2
ZR GANG-PANG
∠
+
3
--------------------------------------------------------
------------------------------------------------------------------
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...