ABB REL 356 Current Differential Protection
5-11
Testing
Table 5-1. Zone 2 Phase-Ground Forward Internal Faults: Z2GF = 4.5 Ohms Z2GR = 0.01 Ohms
Volts
Ð
Angle
I
Amps
Ð
Angle
Fault Z
Ohms
Ð
Angle
Relay System
Operation
AG at MTA 90% of reach fault
Va = 30
Ð
0
Ia = 4.4
Ð
-75 (285)
4.05
Ð
75
Vb = 69
Ð
-120 (240)
Ib = 0
Vc = 69
Ð
-240 (120)
Ic = 0
Z2T Trip
Fault type AG
Z2G Unit
Trip time 100-132 ms
AG at MTA –45
°
90% of reach fault
Va = 30
Ð
0
Ia = 6.23
Ð
-30 (330)
2.86
Ð
30
Vb = 69
Ð
-120 (240)
Ib = 0
Vc = 69
Ð
-240 (120)
Ic = 0
Z2T Trip
Fault type AG
Z2G Unit
Trip time 100-132 ms
AG at MTA +45˚ 90% of reach fault
Va = 30
Ð
0
Ia = 6.23
Ð
-120 (240)
2.86
Ð
120
Vb = 69
Ð
-120 (240)
Ib = 0
Vc = 69
Ð
-240 (120)
Ic = 0
Z2T Trip
Fault type AG
Z2G Unit
Trip time 100-132 ms
BG at MTA 90% of reach fault
Va = 69
Ð
0
Ia = 0
4.05
Ð
75
Vb = 30
Ð
-120 (240)
Ib = 4.4
Ð
-195 (165)
Vc = 69
Ð
-240 (120)
Ic = 0
Z2T Trip
Fault type BG
Z2G Unit
Trip time 100-132 ms
BG at MTA –45˚ 90% of reach fault
Va = 69
Ð
0
Ia = 0
2.86
Ð
30
Vb = 30
Ð
-120 (240)
Ib = 6.23
Ð
-150 (210)
Vc = 69
Ð
-240 (120)
Ic = 0
Z2T Trip
Fault type BG
Z2G Unit
Trip time 100-132 ms
BG at MTA +45˚ 90% of reach fault
Va = 69
Ð
0
Ia = 0
2.86
Ð
120
Vb = 30
Ð
-120 (240)
Ib = 6.23
Ð
-240 (120)
Vc = 69
Ð
-240 (120)
Ic = 0
Z2T Trip
Fault type BG
Z2G Unit
Trip time 100-132 ms
CG at MTA 90% of reach fault
Va = 69
Ð
0
Ia = 0
4.05
Ð
75
Vb = 69
Ð
-120 (240)
Ib = 0
Vc = 30
Ð
-240 (120)
Ic = 4.4
Ð
-315 (45)
Z2T Trip
Fault type CG
Z2G Unit
Trip time 100-132 ms
CG at MTA –45˚ 90% of reach fault
Va = 69
Ð
0
Ia = 0
2.86
Ð
30
Vb = 69
Ð
-120 (240)
Ib = 0
Vc = 30
Ð
-240 (120)
Ic = 6.23
Ð
-270 (90)
Z2T Trip
Fault type CG
Z2G Unit
Trip time 100-132 ms
CG at MTA +45˚ 90% of reach fault
Va = 69
Ð
0
Ia = 0
2.86
Ð
120
Vb = 69
Ð
-120 (240)
Ib = 0
Vc = 30
Ð
-240 (120)
Ic = 6.23
Ð
0
Z2T Trip
Fault type CG
Z2G Unit
Trip time 100-132 ms
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...