ABB REL 356 Current Differential Protection
5-15
Testing
5.
Forward External Faults
For forward Zone 2 Phase-Ground External faults use the Table 5-5 of voltages and currents. In each case apply the 3-
phase voltage to the relay system first then suddenly apply the currents listed. The relay system should not trip as
these faults are beyond the reach of the Zone 2 ground units.
Table 5-5. Zone 2 Phase-Ground Forward External Faults: Z2GF = 4.5 Ohms Z2GR = 4.5 Ohms
Volts
∠
Angle
I
Amps
∠
Angle
Fault Z
Ohms
∠
Angle
Relay System
Operation
AG at MTA 110% of reach fault
Va = 30
∠
0
Ia = 3.6
∠
-75 (285)
4.95
∠
75
Vb = 69
∠
-120 (240)
Ib = 0
Vc = 69
∠
-240 (120)
Ic = 0
No trips
AG at MTA –45˚ 110% of reach fault
Va = 30
∠
0
Ia = 3.6
∠
-30 (330)
4.95
∠
30
Vb = 69
∠
-120 (240)
Ib = 0
Vc = 69
∠
-240 (120)
Ic = 0
No trips
AG at MTA +45˚ 110% of reach fault
Va = 30
∠
0
Ia = 3.6
∠
-120 (240)
4.95
∠
120
Vb = 69
∠
-120 (240)
Ib = 0
Vc = 69
∠
-240 (120)
Ic = 0
No trips
BG at MTA 110% of reach fault
Va = 69
∠
0
Ia = 0
4.95
∠
75
Vb = 30
∠
-120 (240)
Ib = 3.6
∠
-195 (165)
Vc = 69
∠
-240 (120)
Ic = 0
No trips
BG at MTA –45˚ 110% of reach fault
Va = 69
∠
0
Ia = 0
4.95
∠
30
Vb = 30
∠
-120 (240)
Ib = 3.6
∠
-150 (210)
Vc = 69
∠
-240 (120)
Ic = 0
No trips
BG at MTA +45˚ 110% of reach fault
Va = 69
∠
0
Ia = 0
4.95
∠
120
Vb = 30
∠
-120 (240)
Ib = 3.6
∠
-240 (120)
Vc = 69
∠
-240 (120)
Ic = 0
No trips
CG at MTA 110% of reach fault
Va = 69
∠
0
Ia = 0
4.95
∠
75
Vb = 69
∠
-120 (240)
Ib = 0
Vc = 30
∠
-240 (120)
Ic = 3.6
∠
-315 (45)
No trips
CG at MTA –45˚ 110% of reach fault
Va = 69
∠
0
Ia = 0
4.95
∠
30
Vb = 69
∠
-120 (240)
Ib = 0
Vc = 30
∠
-240 (120)
Ic = 3.6
∠
-270 (90)
No trips
CG at MTA +45˚ 110% of reach fault
Va = 69
∠
0
Ia = 0
4.95
∠
120
Vb = 69
∠
-120 (240)
Ib = 0
Vc = 30
∠
-240 (120)
Ic = 3.6
∠
0
No trips
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...