ABB REL 356 Current Differential Protection
5-25
Testing
The apparent impedances seen by the relay in each of the above positions and the expected operation of the inner (21
BI) and outer (21 BO) blinders are the following:
Test #1 indicates the sequence of positions in the RX diagram to be applied and the time in cycles to hold the
position and the action of the relay.
The fault impedance measured should be 10.6
Ð
105 ohms.
V (Volts)
I (Amps)
1
Va = 69
Ð
0
Vb = 69
Ð
-120
Vc = 69
Ð
+120
Ia = 5
Ð
-5
Ib = 5
Ð
-125
Ic = 5
Ð
+115
2
Va = 20
Ð
0
Vb = 20
Ð
-120
Vc = 20
Ð
+120
Ia = 4.5
Ð
-25
Ib = 4.5
Ð
-145
Ic = 4.5
Ð
+95
3
Va = 20
Ð
0
Vb = 20
Ð
-120
Vc = 20
Ð
+120
Ia = 6
Ð
-65
Ib = 6
Ð
+175
Ic = 6
Ð
+55
4
Va = 20
Ð
0
Vb = 20
Ð
-120
Vc = 20
Ð
+120
Ia = 4
Ð
-100
Ib = 4
Ð
+140
Ic = 4
Ð
+20
5
Va = 69
Ð
0
Vb = 69
Ð
-120
Vc = 69
Ð
+120
Ia = 6.5
Ð
-105
Ib = 6.5
Ð
+135
Ic = 6.5
Ð
+15
POS
Z app
21 BI
41 BO
1
13.8
∠
5
No
No
2
4.47
∠
25
No
Yes
3
3.33
∠
65
Yes
Yes
4
5.00
∠
100
No
Yes
5
10.6
∠
105
No
No
TEST #1
Trip OST on the Way Out
Pos
Time
Trip Action
A
1
60
2
5
3
20
4
5
5
60
50-67 ms after 2
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...