ABB REL 356 Current Differential Protection
6-4
Computer Communications
Table 6-2. RS-PONI Dip Switch Settings
Dip Switch Pole
Port Data
Rate
1
2
3
bps
0
0
0
300
0
0
1
1200
0
1
0
2400
0
1
1
4800
1
0
0
9600
1
0
1
19200
1
1
0
1200
1
1
1
1200
Dip Switch Pole
Auto Answer
Rings
4
5
0
0
none
0
1
4
1
0
8
1
1
12
NOTE:
Turn the power OFF and ON, anytime
Dip Switch changes are made.
Fault Record Data Definitions
The Oscillographic and Recording Program (OSCAR) under selection: “Load Screen Layout File” of the main menu offers
the following display files for REL 356.
Analog Signals
The following signals are displayed on the main OSCAR screen following a download of both analog and digital signals
from the REL 356 relay:
la
phase A current
lb
phase B current
lc
phase C current
-3I0
zero sequence current (note the negative sing)
Vag
phase A to ground voltage
Vbg
phase B to ground voltage
Vcg
phase C to ground votlage
It
local current after sequence filter
Vflr
real part of local It current
These additional analog signals are displayed by F1 - ANA MENU:
Vfli
imaginary part of local It current
Vfrr*
real part of remote It current
Vfri*
imaginary part of remote It current
Op
operating value
Res
restraint value
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...