LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY
Page 4 of 53
SEGMENT 3: LOGIC REQUIRED FOR EACH STEP IN THE RESTORATION SEQUENCE FOR
CALCULATION AND CONTROL. HMI LOGIC FOR TRIGGERNG MESSAGES AND ALARMS IN THE
MAGELIS SYSTEM.
SEGMENT 4: ANCILLARY SUBROUTINES providing 32 bit number conversion since the Compact 984
does not easily allow for mathematics on a double register number or single register number containing a
value of 9999 or greater. The ABB products allow numbers to be reported in a single register interpreted
as 0 to 65535 (Unipolar) or –32767 to 32768 (Bipolar). If a number is a 32 bit representation, PLC logic
must be added to the specific vendor’s PLC allow computations to occur.
Compact PLC
Segment 1
Compact PLC
reads
ABB
DPU
2000R via Modbus
Plus. (Path A)
The Compact PLC
reads
1. New Alarm Status
2. Currents
3. Voltages
4. Power
5. Status
The Compact PLC
can perform MANUAL
or AUTOMATIC
CONTROL.
1. TRIP
2. RESET TARGETS
3. RESET ALARMS
4. RESET LATCHES
The Compact PLC
serves as a data
concentrator
Path A
Modbus Plus Network
TPU 2000R
Figure 2. Modbus Plus Ladder Logic Implementation Strategy
The Ladder Logic is Segment 1 is very straight forward. Figure 3 illustrates the method of obtaining the
data from the TPU2000R via Modbus Plus.
The data requested includes logical element status which includes breaker trip information for phases A,
B, and C. The phase information is latched, and its status must be reset by the operator to annunciate
the alarm which is decoded by the PLC.
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...