ABB REL 356 Current Differential Protection
1-2
Product Overview and Specifications
For an internal fault, the currents are essentially in phase at the terminals of the transmission line. For an external fault,
the currents are 180
°
out of phase. Figure 1-1 illustrates the concept.
Figure 1-1. Fault Recognition
Standard Features
·
Current differential protection algorithm
·
Numerical processing
·
Multiple microprocessor design
·
Current change detectors and selectable voltage change detectors
·
Direct transfer trip
·
Channel independent high set phase and ground overcurrent units, directional or non-directional
·
Fault locator
·
High speed operation, typical 1½ cycle
·
Close into fault detection
·
Open breaker and stub bus trip
·
Contact outputs for
·
Breaker trip
·
General start
·
Breaker failure initiation
·
Reclose initiate and block
·
System failure alarm
·
Channel failure alarm
·
Trip alarm
·
RS232C series communications port
·
Adaptive protection communication channel delay compensation
·
Digital fault recording
·
10 analog waveforms from local and remote measurements
·
64 digital channels
·
12 samples per cycle
·
Local HMI interface
·
19” rack mounting
Communication Channel Options
REL 356 is available with eight different communication interfaces:
·
9600 bps audiotone
·
British Telecom audiotone
·
56/64 kbps direct digital
·
56/64 kbps 820 nm multi-mode fiber
·
56/64 kbps 1300 nm single mode fiber, short reach
·
56/64 kbps 1300 nm single mode fiber, medium reach
·
56/64 kbps 1300 nm single mode fiber, long reach
·
56/64 kbps direct digital with G.703 interface
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...