LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY
Page 17 of 53
Modbus
via Radio (IED Receiving)
Modbus Address 2
THE
CLOUD
DPU 2000R
Substation Location 2
Modbus Address 1
Modbus
via Radio (Host Sending)
Query DPU for Voltage, Current, Power, Breaker Status and Change of
State Information and store in PLC buffer 41700 through 41849
Query PCD for Voltage, Current, Power, Breaker Status and Change of
State Information and store in PLC buffer 41700 through 41849
Figure 28. Network Topology for Nodes Remote to the PLC and Polled Via Modbus
Command Responses
The ladder logic shall be reviewed for the method to complete the data exchange between the PLC and
the IED’s
SEGMENT 3 NETWORK 1:
The FIFO used to gather the information from the IED’s is reset whenever data is transferred into the
FIFO for polled queue. This is a standard instruction construct which is similar to that used for the MSTR
instruction.
Figure 29. Segment 3 Network 1 – FIFO Entry for XMIT Instruction Notification
SEGMENT 3 NETWORK 2:
The network is a cyclical poll which pages the 10 instructions to the XMIT to gather data from the two
IED’s (PCD2000 and the DPU2000R). The UCTR instruction increments between 1 and 10. The Pointer
is then multiplied by 10 (stored in 40333) which serves as the pointer to the 6X command buffer which
parameterizes the XMIT instruction to retrieve the IED’s data.
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...