ABB REL 356 Current Differential Protection
1-6
Product Overview and Specifications
Binary (Voltage) Input Circuits
Jumper selectable
48, 125 or 250 Vdc
Drop-out threshold
67%
9600 bps Audio Tone Communication Interface
Operating speed
9600 bps
Standards compliance
ITU V.29
Carrier frequency
1,700 Hz
Modulation QAM – Quadrature Amplitude Modulation
Transmit level - 1 dBm to – 15 dBm in 2 dBm steps
Receiver sensitivity - 33 dBm
Channel requirement 4 wire, unconditioned
56/64 kbps Digital Communication
Operating speed
56 or 64 kbps, selectable
Direct digital option
Electrical standard
RS422/RS485
Mechanical standard
RS530
Maximum distance
4000’/1300 m
Fiber optic options
Connector
ST
Wave length 820 nm
Cable
multi-mode
Transmitter output into 50/125
m
m cable
- 18 dBm minimum
Receiver input - 28 dBm minimum
Reach, typical 2 miles/3.3 km
Wave length 1300 nm
Cable
single-mode
Transmitter output into 9/125
m
m cable
Short reach option
- 20 dB minimum
Reach, typical
7.5 miles/12 km
Medium reach option
- 10 dB minimum
Reach, typical
20 miles/32 km
Long reach option
0 dB minimum
Reach, typical
32 miles/52 km
Receiver input
- 32 dBm minimum
- 20 dBm maximum
*
* Receiver maximum input is determined by receiver saturation and should not be exceeded. An attenuator is
delivered to facilitate back-to back testing. The received level should be adjusted to – 26 dBm.
Optional G.703 Interface
The optional G.703 interface adapter complies with CCITT (ITU) G.703 co-directional, 64 kbps specification. For
details refer to IL 40-201.7
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...