ABB REL 356 Current Differential Protection
1-7
Product Overview and Specifications
Optional Computer/Network Interface
·
RS232C PONI
for single point computer communications
·
RS232C PONI with IRIG-B
for modulated/de-modulated IRIG-B time synchronization
·
Modbus PONI
for DNP 3.0 network communications (requires an external MIPC card)
·
INCOM PONI
for local network communications using INCOM network
Chassis Dimensions and Weight
Height
7” (177.8 mm), 4 rack units
Width
19” (482.6 mm)
Depth including terminal blocks
14” (356 mm)
Weight
68 lb (17.5 kg)
Environmental Data
Ambient temperature range
Operation
- 20
°
C to + 60
°
C
Storage
- 40
°
C to + 80
°
C
Insulation test voltage, ANSI C37.90, IEC 255-5 2.8 kV dc, 1 minute
3.2 kV dc, 1 second
Open contacts
1400 V dc, continuous
Impulse voltage withstand, IEC 255-5
1.2/50
m
s, 0.5 Joule
Surge withstand voltage, ANSI C37.90.1, IEC 255-22-1
3 kV, 1 MHz
Fast transient voltage, ANSI C37.90.1, IEC 255-22-4
4 kV, 10/100 ns
EMI field strength withstand, ANSI C37.90.2
25 MHz – 1 GHz, 10 V/m
Emission tests, EN 50081-1, class A
Conducted emissions
150 kHz – 30 MHz
Radiated emissions
30 MHz – 1000 MHz
CT Requirements for REL356 Current Differential Protection
REL356 uses the operating principle of comparing an operating quantity OP with a restraint quantity RES. The operating
quantity is formed from:
TL
TR
I
I
OP
+
=
where ITR
is the remote composite current and ITL is the local composite current. ITR and ITL are formed by local and
remote currents, respectively, in the following manner:
0
2
2
1
1
0
I
C
I
C
I
C
I
T
+
+
−
=
The restraint quantity is formed from:
TL
TR
I
I
RES
+
=
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...