ABB REL 356 Current Differential Protection
2-10
Installation, Operation and Maintenance
There are 2 ways to reset the targets:
• Using the “Target Reset” Contact Input.
• With the INCOM command, using the communication channel.
Test Mode Function
The test display mode provides diagnostic and testing capabilities for REL 356. Relay status display, local delay time
computation, and relay testing are among the functions provided. The test mode functions are listed in Table 2-1.
Table 2-1. Test Mode Functions
Contact Input Test
The Contact Input module can be conveniently tested, using the Contact Input Test Function.
To activate this function, continually depress the DISPLAY key until the “TEST” LED is illuminated. Then depress the
“FUNCTION RAISE’ or “FUNCTION LOWER” key until the word “OPTI” appears in the FUNCTION field.
The “VALUE” field will display the status of the contact inputs, using two hexadecimal digits, as explained below.
When the contacts close (voltage is applied across two input terminals), the corresponding bit is set to binary “1”; an
open set of contacts results in a binary “0”. The following correspondence exists:
FUNCTION
BIT NUMBER
Direct Transfer Trip
0
Stub Bus
1
Differential Protection Disable
2
Target Reset
3
52b
4
Not Used
5
Not Used
6
Not Used
7
Function
Description
STAT
SRT
Relay Self-Check Status
Monitor Standing Relay Trip Signal
OPTI
Display Opto Input Status
TRIP
BFI
SRI
3RI
RB
GS
FALM
TALM
CALM
Relay Test:
Relay Test:
Relay Test:
Relay Test:
Relay Test:
Relay Test:
Relay Test:
Relay Test:
Relay Test:
Trip Relays
BFI Relays
RI Relay (RI1)
RI Relay (RI2)
Reclose Block Relay
General Start Relay
Failure Alarm Relay
Trip Alarm Relay
Channel Alarm Relay
As soon as a fault event is detected, the most recent two sets of target data are available for display. The “LAST
FAULT” is the data associated with the most recent trip event. The “PREVIOUS FAULT” contains the data from the prior
trip event. If a single fault occurs, the “LAST FAULT” LED flashes. If a reclosing is applied and the system trips, the
original “LAST FAULT” information will be transferred to the “PREVIOUS FAULT” memory. The latest trip information will
be stored in the “LAST FAULT” memory, and its LED flashes twice per second. To reset the flashing LEDs, depress the
“Reset Targets” key once. The target information in “LAST FAULT” and “PREVIOUS FAULT”, will not be reset from the
front panel key switch.
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...