ABB REL 356 Current Differential Protection
2-12
Installation, Operation and Maintenance
(4) Activate the “ENTER” key for the desired duration of the output relays operation.
(5) Depress the “FUNCTION RAISE” key to select the following parameters, as desired:
FUNCTION
VALUE
FIELD
FIELD
DESCRIPTION
TRIP
RELY
TRIP (A, B, C)
* BFI
RELY
Breaker Failure Initiate
* RI (RI1-1,2)
RELY
Single Pole Reclose Initiate
* RI (RI2-1,2)
RELY
3 Pole Reclose Initiate
RB
RELY
Recloser Blocking
GS
RELY
General Start
FALM
RELY
Failure Alarm
TALM
RELY
Trip Alarm
CALM
RELY
Channel Alarm
Note: * These outputs are enabled only if a connection is made from TB1-13 to TB1-14.
(6) Activate the “ENTER” key to operate selected output relays.
(7) After completion of this test, restore the system to its operating state by moving JM1 to position 2-3 on the
Microprocessor module, and closing the FT switch red handles.
Self Check
The results of the system self-check routines are accessible using the following procedure:
a. Continually depress the “DISPLAY” key until the “TEST” LED is illuminated; then depress the “FUNCTION
RAISE” or “FUNCTION LOWER” key until the word “STAT” appears in the FUNCTION FIELD.
b. The VALUE FIELD will display the status of the relay in hexadecimal format:
RELAY STATUS
DESCRIPTION
BIT NUMBER
External RAM Failure
0 Least Significant Right-Most Position
EEPROM Failure
1
ROM Checksum Failure
2
Dual-Port RAM Failure
3
Analog Input Failure
4
Processor Failure
5
± 12V P.S.Fail
6
Modem Failure
7
EEPROM Warning
8
Power Supply 1 Failure
9
Power Supply 2 Failure
10
Dual Port RAM
Com Status Warning
11
Failure Detected by Processor 1
12
Failure Detected by Processor 2
13
0
14
0
15 Most Significant Left-Most Position
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...