ABB REL 356 Current Differential Protection
3-3
Settings and Application
Table 3-1. Setting Table Continued
RU
OST1
OST2
OST3
OSOT
SETR
TIME
YEAR
MNTH
DAY
WDAY
HOUR
MIN
XX.XX
XX.XX
XX.XX
XX.XX
XX.XX
YES/NO
YES/NO
XXXX
XX
XX
SUN/MON/TUES/WED/THUR/FRI/SAT
XX
XX
3.00
0.50
0.50
0.50
24
1980
1
1
0
0
1.00
Z3P
XX.XX
0.01
Zone 3 phase distance setting in ohms
T3P
XX.XX
0.10
Zone 3 phase time delay in seconds
Z2GF
XX.XX
0.01
Zone 2 ground forward distance setting in ohms
Z2GR
XX.XX
0.01
Zone 2 ground reverse distance setting in ohms
T2G
XX.XX
0.00
Zone 2 ground time delay in seconds
Z3GF
XX.XX
0.01
Zone 3 ground forward distance setting in ohms
Z3GR
XX.XX
0.01
Zone 3 ground reverse distance setting in ohms
T3G
XX.XX
0.10
Zone 3 ground time delay in seconds
OST
NO/WAYI/WAYO
Out-of-step trip enable
OSB
NONE/Z2/Z3/BOTH
Enable out-of-step blocking for backup protection
R T
XX.XX
15.00
5.0
4.00
5.0
240
2079
1 2
3 1
2 3
5 9
50.00
2.99
50.00
50.00
2.99
50.00
50.00
2.99
15.00
0.10
0.05
0.05
0.05
1
1
1
1
1
1
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.10
ohms
cycles
cycles
cycles
cycles
year
month
d a y
hour
minute
ohms
sec
ohms
ohms
sec
ohms
ohms
sec
ohms
4, 8
3, 8
8
8
8
4, 8
2, 8
4, 8
4, 8
2, 8
4, 8
4, 8
2, 8
8
8
4, 8
Inside blinder setting in ohms
Note 1:
For 5 A relay. Setting and step are a factor of 5 lower for 1 A relay.
Note 3:
These settings have a "OUT" option for disabling a corresponding function.
Note 4:
The impedance setting. The setting ranges shown are for 5 A ct. The displayed setting range is multiplied by 5 if a 1 A ct is
used (CTYP = 1).
Note 5:
9600 bps Audio Tone option.
Note 2:
These settings have a "BLK" option for disabling a corresponding function.
Note 6:
56/64 kbps Digital Communication option.
Note 7:
Only if optional extended output is included.
Note 8:
Only if optional backup system is included.
Setting
Format
Min
Max
Step
Units
Notes
Name
Outside blinder setting in ohms
Out-of-step block timer
Out-of-step trip-on-the-way-in timer
Out-of-step trip-on-the-way-out timer
Out-of-step override timer in milliseconds
Enable INCOM remote setting feature
Enable setting of real time clock
RTC setting year
RTC setting month
RTC setting day
RTC setting day of week
RTC setting hours
RTC setting minutes
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...