Configurable logic blocks (CL1)
Chapter 3
Common functions
Table 43:
Input signals for the TIMERLONG (TLnn-) function block
Path in local HMI: ServiceReport/Functions/TimerLong
Table 44:
Output signals for the TIMERLONG (TLnn-) function block
6.6.1
Setting parameters
Table 45:
Setting parameters for the TimerLong (TLnn-) function
6.7
Pulse timer function block (TP)
The pulse function can be used, for example, for pulse extensions or limiting of operation of out-
puts. The pulse timer TP has a settable length.
Table 46:
Input signals for the TP (TPnn-) function block
Path in local HMI: ServiceReport/Functions/Pulsen
Signal
Description
INPUT
Input to long timer
T
Time value. See setting parameters
Signal
Description
OFF
Output from long timer, drop-out delayed
ON
Output from long timer, pick-up delayed
xx00000162.vsd
TL01-
TIMERLONG
INPUT
T
OFF
ON
Parameter
Range
Default
Unit
Description
T
0.0-90000.0
Step:0.1
0.0
s
Delay for TLnn function. Can only be set
from CAP configuration tool.
Signal
Description
INPUT
Input to pulse timer
T
Pulse length. See setting parameters
xx00000163.vsd
TP01-
PULSE
INPUT
T
OUT
Summary of Contents for REL 501-C1 2.5
Page 1: ...Technical reference manual Line distance protection terminal REL 501 C1 2 5 ...
Page 2: ......
Page 26: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 42: ...30 Technical data Chapter 2 General ...
Page 66: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 142: ...130 Time delayed overvoltage protection TOV Chapter 6 Voltage ...
Page 162: ...150 Autorecloser AR Chapter 9 Control ...
Page 174: ...162 Event function EV Chapter 10 Logic ...
Page 210: ...198 Serial communication Chapter 12 Data communication ...
Page 226: ...214 Serial communication modules SCM Chapter 13 Hardware modules ...
Page 230: ...218 Terminal diagrams Chapter 14 Diagrams Figure 87 REL 501 C1 with DC switch ...
Page 234: ...222 Terminal diagrams Chapter 14 Diagrams ...
Page 237: ......