51
Configurable logic blocks (CL1)
Chapter 3
Common functions
Table 59:
Input signals for the GT (GTnn-) function block
Path in local HMI: ServiceReport/Functions/ControlGates1/FuncOutputs
Table 60:
Output signals for the GT (GTnn-) function block
6.12.1
Setting parameters
Path in local HMI: Settings/Functions/Groupn/ContrGates1/Gaten
Table 61:
Setting parameters for the GT (GTnn-) function
6.13
Settable timer function block (TS)
The function block TS timer has outputs for delayed input signal at drop-out and at pick-up. The
timer has a settable time delay. It also has an Operation setting On, Off that controls the opera-
tion of the timer.
Table 62:
Input signals for the TS (TSnn-) function block
Path in local HMI: ServiceReport/Functions/TimerSet1/FuncOutputs
Signal
Description
INPUT
Input to gate
Signal
Description
Out
Output from gate
xx00000380.vsd
GT01-
GT
INPUT
OUT
Parameter
Range
Default
Unit
Description
Operation
Off/On
Off
-
Operating mode for GTn function
Signal
Description
INPUT
Input to timer
xx00000381.vsd
TS01-
TS
INPUT
ON
OFF
Summary of Contents for REL 501-C1 2.5
Page 1: ...Technical reference manual Line distance protection terminal REL 501 C1 2 5 ...
Page 2: ......
Page 26: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 42: ...30 Technical data Chapter 2 General ...
Page 66: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 142: ...130 Time delayed overvoltage protection TOV Chapter 6 Voltage ...
Page 162: ...150 Autorecloser AR Chapter 9 Control ...
Page 174: ...162 Event function EV Chapter 10 Logic ...
Page 210: ...198 Serial communication Chapter 12 Data communication ...
Page 226: ...214 Serial communication modules SCM Chapter 13 Hardware modules ...
Page 230: ...218 Terminal diagrams Chapter 14 Diagrams Figure 87 REL 501 C1 with DC switch ...
Page 234: ...222 Terminal diagrams Chapter 14 Diagrams ...
Page 237: ......