29
Making the electrical connections
&KDSWHU
,QVWDOOLQJWKHWHUPLQDO
)LJXUH &RQQHFWHGFDEOHVZLWKIHUUXOHV
If the terminal is equipped with a test-switch of type RTXP 24 Combiflex wires with
20 A sockets must be used to connect the VT circuits and the auxiliary power.
&RQQHFWLQJWRSURWHFWLYHJURXQG
Connect the unit to the grounding bar of the cubicle with a green/yellow conductor,
cross section at least 1.5 mm
2
(AWG16), connected to the protective ground connector
at the back of the terminal.
0DNLQJWKHVFUHHQFRQQHFWLRQ
When using screened cables always make sure screens are grounded and connected in
according to applicable engineering methods. This may include checking for appropri-
ate grounding points near the terminal, for instance, in the cubicle and/or near the source
of measuring. Ensure that ground connections are made with short (max. 10 cm) con-
ductors of an adequate cross section, at least 6 mm
2
(AWG10) for single screen connec-
tions.
Where:
1
is ferrules
en0300087.vsd
Rx
Tx
Sc
Lc
Tx
Rx
Sc
Lc
Cc
Relay
Terminal
External
Equipment