GUID-C6C98FE0-F559-45EE-B853-464516775417 v3
Table 84. Number of TIMERSET instances
Logic block
Quantity with cycle time
Range or Value
Accuracy
3 ms
8 ms
100 ms
TIMERSET
15
15
30
(0.000–90000.000) s
±0.5% ±10 ms
GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2
Table 85. Number of XOR instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
XOR
10
10
20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v4
Table 86. Number of B16I instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
B16I
6
4
8
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2
Table 87. Number of BTIGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
BTIGAPC
4
4
8
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v3
Table 88. Number of IB16 instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
IB16
12
4
8
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2
Table 89. Number of ITBGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
ITBGAPC
4
4
8
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4
Table 90. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
Function
Cycle time (ms)
Range or value
Accuracy
Elapsed time integration
3
0 ~ 999999.9 s
±0.2% or ±20 ms whichever is
greater
8
0 ~ 999999.9 s
±0.2% or ±100 ms whichever is
greater
100
0 ~ 999999.9 s
±0.2% or ±250 ms whichever is
greater
Line distance protection REL650
1MRK 506 384-BEN H
Version 2.2
86
Hitachi Power Grids
© 2017 - 2021 Hitachi Power Grids. All rights reserved