Section 12
Troubleshooting
12.1
Checking the self supervision signals
IP1474-1 v1
12.1.1
Checking the self supervision function
IP1473-1 v1
12.1.1.1
Determine the cause of an internal failure
M11657-2 v1
This procedure describes how to navigate the menus in order to find the cause of an
internal failure when indicated by the flashing green LED on the HMI module.
Procedure
1.
Display the general diagnostics menu.
Navigate the menus to:
Diagnostics/IED status/General
2.
Scroll the supervision values to identify the reason for the failure.
Use the arrow buttons to scroll between values.
12.1.2
Self supervision HMI data
IP1472-1 v1
12.1.2.1
General IED status
GUID-A84F3903-8A70-47D6-8613-AD7FF8BA3AEC v1
The following table shows the general IED status signals.
M11656-1 v2
Table 20:
Signals from the General menu in the diagnostics tree.
Indicated result
Possible reason
Proposed action
Internal fail Off
No problem detected.
None.
Internal fail On
A failure has occurred.
Check the rest of the indicated results to find
the fault.
Internal warning Off
No problem detected.
None.
Internal warning On
A warning has been
issued.
Check the rest of the indicated results to find
the fault.
Time synch Ready
No problem detected.
None.
Time synch Fail
No time synchronization.
Check the synchronization source for
problems.
If the problem persists, contact your ABB
representative for service.
Real time clock Ready
No problem detected.
None.
Real time clock Fail
The real time clock has
been reset.
Set the clock.
Table continues on next page
1MRK 506 383-UEN A
Section 12
Troubleshooting
Line distance protection REL650 2.2 IEC
183
Commissioning manual
Summary of Contents for REL650 series
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Page 2: ......
Page 24: ...18...
Page 28: ...22...
Page 38: ...32...
Page 54: ...48...
Page 58: ...52...
Page 178: ...172...
Page 182: ...176...
Page 188: ...182...
Page 196: ...190...
Page 206: ...200...
Page 207: ...201...