background image

Installation of A1 breaker:

Mount breaker on its plate, with the straps aligned 
with busbars on the meter-module

Installation of A2 breaker:

Mount breaker on its plate, with the straps aligned 
with busbars on the meter-module

•  Use the mounting screws included in the breaker 

package to fasten the breaker to the plate. Do not 
torque mounting screws completely.

•  Use the 5/16 diameter bolt, 5/16 spring-washer and 

5/16 flat washers, included in the breaker package 
to fasten the breaker straps to the module busbars. 
Torque to 170 in-lbf.

•  Complete the fastening of the breaker to its mount-

ing plate by torquing the mounting screws to 10 in-lbf.

•  The breaker is ready to receive load conductors.
•  Torque the conductors as per indication on the 

breaker itself.

•  Use the mounting screws included in the breaker 

package to fasten the breaker to the plate. Do not 
torque mounting screws completely.

•  Use the 5/16 diameter bolt, 5/16 spring-washer and 

5/16 flat washers, included in the breaker package 
to fasten the breaker straps to the module busbars. 
Torque to 170 in-lbf.

•  Complete the fastening of the breaker to its mounting 

plate by torquing the mounting screws to 10 in-lbf.

Torque to 10 in-lbf

Torque to 10 in-lbf

Torque to 170 in-lbf

Torque to 170 in-lbf

electrification.us.abb.com/reliamod

1T

Q

C

13

30

00

E

00

0

2 R

ev

.A

 S

ep

te

m

b

er

 2

0

23


ABB Inc.
305 Gregson Drive
Cary, NC 27511
United States

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With regard 
to purchase orders, the agreed particulars 
shall prevail. ABB Inc. does not accept any 
 responsibility whatsoever for potential 
errors or possible lack of information 
in this document.

We reserve all rights in this document 
and in the subject matter and illustrations 
contained therein. Any reproduction, 
disclosure to third parties or utilization  
of its contents – in whole or in parts – is 
forbidden without prior written consent 
of ABB Inc.  Copyright© 2023 ABB
All rights reserved

•  Install the phase-barrier on the load-side.
•  The breaker is ready to receive load conductors.
•  Torque the conductors as per indication on the 

breaker itself.

•  Install the terminal cover once the conductors  

are installed.

Reviews: