Function
IEC 61850
A
UE/C101
Residual voltage measurement
RESVMMXU
1
Frequency measurement
FMMXU
1
Other
Input switch group
ISWGAPC
10
Output switch group
OSWGAPC
20
Selector
SELGAPC
6
Minimum pulse timer (2 pcs)
TPGAPC
10
Move (8 pcs)
MVGAPC
1
1, 2, ... = Number of included instances. The instances of a protection function represent the number of
identical protection function blocks available in the standardized configuration.
() = optional
2.3
Indications
Table 3:
Explanations of the indications table columns
Column name
Description
BitA
Default 0X and 1X bit address for the data.
RegA
Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the value states.
2.3.1
Premapped indications
2.3.1.1
Common data 1
Table 4:
Common data 1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
2720
170.00
.Loc.stVal
-
Remote/Local state
0/1=Rem/Loc
2721
170.01
.LocKeyHMI.stVal.Statio
n
-
Station state
1=Station
DR.RDRE1
2722
170.02
.RcdMade.stVal
-
DR recording made
1=Made
2723
170.03
.mcd
Section 2
1MRS758336 B
Modbus data mappings
12
REU611
Point List Manual