BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.FRPFRC2
Frequency gradient
3054
190.14
.Op.general
OPR_FRG
Operate
1=Operate
3055
190.15
.mcd
2.3.1.8
LD0.LEDGGIO1 Indication LED states Color1/Color2
These LED indication points interpret the case when a signal is wired to both the OK
and ALARM inputs, but inverted to the other. This means that the LED toggles
between red and green colors. The default color for ALARM is red and green for OK.
Colors can, however, be reconfigured with a setting parameter.
OK
ALARM
RESET
LEDx
Signal
NOT
GUID-2AE4D47A-2BBD-4422-A81C-CF2EB7473379 V1 EN
Figure 2:
Signal wired to both OK and ALARM inputs – inverted to the other
If the OK and ALARM inputs are wired to separate indication signals,
the LED will have three legal states and cannot be expressed with one
bit only. In this case, it is possible to combine this LED bit
interpretation with the corresponding value from the other LED state
interpretation.
OK
ALARM
RESET
LEDx
Signal 1
Signal 2
GUID-051741E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN
Figure 3:
Separate signals wired to OK and ALARM inputs
Table 11:
LD0.LEDGGIO1 Indication LED states Color1/Color2
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.LEDGGIO1
3520
220.00
.LEDSt1.stVal
-
LED 1 state
0/1=Color1/2
3521
220.01
.LEDSt2.stVal
-
LED 2 state
0/1=Color1/2
3522
220.02
.LEDSt3.stVal
-
LED 3 state
0/1=Color1/2
Table continues on next page
1MRS758336 B
Section 2
Modbus data mappings
REU611
15
Point List Manual