2.3.1.21
LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
Table 24:
LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PSPTUV1
3008
188.00
.Str.general
START
General start
1=Start
3009
188.01
.mcd
3016
188.08
.Op.general
OPERATE
General operate
1=Operate
3017
188.09
.mcd
2.3.1.22
LD0.PSPTUV2 Positive-sequence undervoltage protection (2)
Table 25:
LD0.PSPTUV2 Positive-sequence undervoltage protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PSPTUV2
3018
188.10
.Str.general
START
General start
1=Start
3019
188.11
.mcd
3026
189.02
.Op.general
OPERATE
General operate
1=Operate
3027
189.03
.mcd
2.3.1.23
LD0.RESVMMXU1 Residual voltage measurement (1)
Table 26:
LD0.RESVMMXU1 Residual voltage measurement (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.RESVMMXU1
2764
172.12
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2765
172.13
.mcd
2766
172.14
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2767
172.15
.mcd
2.3.1.24
LD0.ROVPTOV1 Residual overvoltage protection (1)
Table 27:
LD0.ROVPTOV1 Residual overvoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV1
2976
186.00
.Str.general
START
General start
1=Start
2977
186.01
.mcd
2978
186.02
.Op.general
OPERATE
General operate
1=Operate
2979
186.03
.mcd
Section 2
1MRS758336 B
Modbus data mappings
22
REU611