2.3.1.25
LD0.ROVPTOV2 Residual overvoltage protection (2)
Table 28:
LD0.ROVPTOV2 Residual overvoltage protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV2
2980
186.04
.Str.general
START
General start
1=Start
2981
186.05
.mcd
2982
186.06
.Op.general
OPERATE
General operate
1=Operate
2983
186.07
.mcd
2.3.1.26
LD0.ROVPTOV3 Residual overvoltage protection (3)
Table 29:
LD0.ROVPTOV3 Residual overvoltage protection (3)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV3
2984
186.08
.Str.general
START
General start
1=Start
2985
186.09
.mcd
2986
186.10
.Op.general
OPERATE
General operate
1=Operate
2987
186.11
.mcd
2.3.1.27
LD0.TCSSCBR1 Trip circuit supervision (1)
Table 30:
LD0.TCSSCBR1 Trip circuit supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR1
2780
173.12
.CircAlm.stVal
ALARM
Supervision alarm
1=Alarm
2781
173.13
.mcd
2.3.1.28
LD0.TCSSCBR2 Trip circuit supervision (2)
Table 31:
LD0.TCSSCBR2 Trip circuit supervision (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR2
2782
173.14
.CircAlm.stVal
ALARM
Supervision alarm
1=Alarm
2783
173.15
.mcd
1MRS758336 B
Section 2
Modbus data mappings
REU611
23
Point List Manual