2.4.1.10
Device ID string
Table 55:
Device ID string
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9000
u16
ASCII coded string
1)
...
9120
u16
1) See the technical manual.
2.4.1.11
Event record structure
Table 56:
Event record structure
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
Selection write:
9250
u16
1
- Num of multiple records
1...10
9251
i16
1
- Read selection
-499…5
Record 1 data to read:
9252
u16
1
- Record sequence num
1...500
9253
u16
1
- Unread records left
0...499
Timestamp of record
9254
u16
1
- Year, Month
Year/Month
9255
u16
1
- Day, Hour
Day/Hour
9256
u16
1
- Minute, Second
Min/Sec
9257
u16
1
- Millisecond
Millisecond
9258
u16
1
Event identification
1)
9259
u16
1
Data object ID1
1)
9260
u16
1
Data object ID2
1)
9261
u16
1
Event data value 1
1)
9262
u16
1
Event data value 2
1)
Record 2 data to read:
If selected
9263
u16
1
- Record sequence num
1...500
9264
u16
1
- Unread records left
0...499
Timestamp of record
9265
u16
1
- Year, Month
Year/Month
9266
u16
1
- Day, Hour
Day/Hour
9267
u16
1
- Minute, Second
Min/Sec
9268
u16
1
- Millisecond
Millisecond
9269
u16
1
Event identification
1)
Table continues on next page
Section 2
1MRS758336 B
Modbus data mappings
32
REU611
Point List Manual