2.4.1.32
LD0.VMMXU1 Voltage demand values (1)
Table 77:
LD0.VMMXU1 Voltage demand values (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.VAVMMXU1
Demand value
1954
u16
1000
.PhV.phsA.cVal.mag.f
U_DMD_A
Phs A amplitude
0.00…4.0
[×Un]
1955
u16
1000
.PhV.phsB.cVal.mag.f
U_DMD_B
Phs B amplitude
0.00…4.0
[×Un]
1956
u16
1000
.PhV.phsC.cVal.mag.f
U_DMD_C
Phs C amplitude
0.00…4.0
[×Un]
1957
u16
1000
.PPV.phsAB.cVal.mag.f
U_DMD_AB
Phs AB amplitude
0.00…4.0
[×Un]
1958
u16
1000
.PPV.phsBC.cVal.mag.f
U_DMD_BC
Phs BC amplitude
0.00…4.0
[×Un]
1959
u16
1000
.PPV.phsCA.cVal.mag.f
U_DMD_CA
Phs CA amplitude
0.00…4.0
[×Un]
2.4.1.33
LD0.VSMSQI1 Sequence voltage measurement (1)
Table 78:
LD0.VSMSQI1 Sequence voltage measurement (1)
RegA
Typ
Scale
IEC 61580 name
SA name
Description
Values
LD0.VSMSQI1
Sequence of voltages
152
u16
1000
.SeqV.c1.instCVal.mag.f
U1_INST
Positive amplitude
0.00...4.00
[×Un]
153
u16
1000
.SeqV.c2.instCVal.mag.f
U2_INST
Negative amplitude
0.00...4.00
[×Un]
154
u16
1000
.SeqV.c3.instCVal.mag.f
U3_INST
Zero amplitude
0.00...4.00
[×Un]
2.4.2
Unmapped registers
Unmapped registers are register data that have no initial Modbus mapping locations,
but can be added to the user-definable Modbus area using the Communication
Management tool in PCM600. The initial register type settings of these objects have
little meaning, since it is always possible to redefine the settings completely for the
user-definable register.
2.4.2.1
CTRL.LLN0 Local, Remote, Station, Off and Combinations
Table 79:
CTRL.LLN0 Local, Remote, Station, Off and Combinations
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
u16
1
.LocKeyHMI.stVal
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
0…7
1MRS758336 B
Section 2
Modbus data mappings
REU611