Additionally, all the digital inputs that are connected by default are also enabled with
the setting. Default triggering settings are selected depending on the connected input
signal type. Typically all protection START signals are selected to trigger the
disturbance recorded by default.
3.4.3
Functional diagrams
The functional diagrams describe the default input, output, programmable LED,
switch group and function-to-function connections. The default connections can be
viewed and changed with switch groups in PCM600, LHMI and WHMI according to
the application requirements.
The analog channels have fixed connections towards the different function blocks
inside the protection relay’s configuration. Exceptions from this rule are the four
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.
3.4.3.1
Functional diagrams for protection
The functional diagrams describe the protection functionality of the protection relay
in detail and picture the factory default connections.
LED 4
HIGH-IMPEDANCE DIFFERENTIAL PROTECTION
HIAPDIF1
dHi>(1)
87(1)
BLOCK
OPERATE
I_A
START
HIBPDIF1
dHi>(2)
87(2)
BLOCK
OPERATE
I_B
START
HICPDIF1
dHi>(3)
87(3)
BLOCK
OPERATE
I_C
START
OSWGAPC4
OR
OUT
IN_1
IN_2
IN_3
SELGAPC4
OUT_4
IN_6
LED 1
LED 2
LED 3
OSWGAPC10
OUT
IN_3
OSWGAPC9
OUT
IN_2
OSWGAPC8
OUT
IN_1
SELGAPC4
OUT_3
IN_12
SELGAPC4
OUT_2
IN_11
SELGAPC4
OUT_1
IN_10
HZCCASPVC1_ALARM
HZCCBSPVC1_ALARM
HZCCCSPVC1_ALARM
GUID-4D5EE676-4AC1-4E46-B4C8-641B149B3C83 V2 EN
Figure 16:
High-impedance differential protection
Section 3
1MRS757455 E
REB611 standardized configuration
34
REB611
Application Manual