background image

voltage-dependent resistor (VDR). The value of the primary current I

prim

 at which the

protection relay operates at a certain setting can be calculated using the formula

I

n

I

I

m

I

prim

rs

u

m

= ×

+

+

×

(

)

GUID-2A742729-7244-4B1C-A4DF-404BDD3A68D9 V1 EN

(Equation 5)

I

prim

the primary current at which the protection is to start

n

the turn ratio of the current transformer

I

rs

the value of the 

Operate value setting

I

u

the leakage current flowing through the VDR at the U

s

 voltage

m

the number of current transformers included in the protection per phase

I

m

the magnetizing current per current transformer at the U

s

 voltage

The I

e

 value given in many catalogs is the excitation current at the knee point voltage.

Assuming U

kn

 ≈ 2 × U

s

, the value of 

I

m

I

e

2

 gives an approximate value for 

Equation

5

.

The selection of current transformers can be divided into procedures:

1. The rated current I

n

 of the feeder should be known. The value of I

n

 also affects

how high I

kmax

 is.

2. The rated primary current I

1n

 of the CT must be higher than the rated current of

the feeder.
The choice of the CT also specifies R

in

.

3. The required U

kn

 is calculated using 

Equation 2

. If U

kn

 of the CT is not high

enough, enough, another CT has to be selected. The value of U

kn

 is given by the

manufacturer in the case of Class X current transformers or it can be estimated
using 

Equation 6

.

4. The sensitivity I

prim

 is calculated using 

Equation 5

If the achieved sensitivity is

sufficient, the present CT is chosen. If a better sensitivity is needed, a CT with a
bigger core is chosen.

If other than Class X CTs are used, an estimate for U

kn

 is calculated using the equation:

Section 4

1MRS757455 E

Requirements for measurement transformers

60

REB611

Application Manual

Summary of Contents for Relion 611 Series

Page 1: ...RELION 611 SERIES Busbar and Multipurpose Differential Protection and Control REB611 Application Manual...

Page 2: ......

Page 3: ...Document ID 1MRS757455 Issued 2019 04 10 Revision E Product version 2 0 Copyright 2019 ABB All rights reserved...

Page 4: ...bed in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB G...

Page 5: ...ted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administrat...

Page 6: ...concerning electrical equipment for use within specified voltage limits Low voltage directive 2014 35 EU This conformity is the result of tests conducted by ABB in accordance with the product standar...

Page 7: ...y package version 10 Operation functionality 11 Optional functions 11 Physical hardware 11 Local HMI 12 Display 12 LEDs 13 Keypad 13 Web HMI 14 Command buttons 15 Authorization 16 Audit trail 17 Commu...

Page 8: ...43 Binary outputs and LEDs 43 GOOSE 54 Section 4 Requirements for measurement transformers 57 Current transformers 57 Current transformer requirements for differential protection 57 Section 5 Protecti...

Page 9: ...be used The manual can also be used when calculating settings 1 2 Intended audience This manual addresses the protection and control engineer responsible for planning pre engineering and engineering T...

Page 10: ...oint list manual Cyber security deployment guideline GUID 0777AFDA CADF 4AA9 946E F6A856BDF75E V1 EN Figure 1 The intended use of manuals in different lifecycles Product series and product specific ma...

Page 11: ...rical warning icon indicates the presence of a hazard which could result in electrical shock The warning icon indicates the presence of a hazard which could result in personal injury The caution icon...

Page 12: ...eter values are indicated with quotation marks The corresponding parameter values are On and Off Input output messages and monitored data names are shown in Courier font When the function starts the S...

Page 13: ...hase segregated CT supervision function for phase A instance 1 HZCCASPVC1 MCS 1I 1 MCS 1I 1 Phase segregated CT supervision function for phase B instance 2 HZCCBSPVC1 MCS 1I 2 MCS 1I 2 Phase segregate...

Page 14: ...8...

Page 15: ...tions Once the application specific parameter set has been entered the installed protection relay is ready to be put into service The further addition of communication functionality and interoperabili...

Page 16: ...are closable Ethernet ports Report summary via WHMI 2 1 2 PCM600 and relay connectivity package version Protection and Control IED Manager PCM600 Ver 2 7 or later REB611 Connectivity Package Ver 2 0 o...

Page 17: ...al phase current inputs 1 5 A 1 residual current input 1 5 A or 0 2 1 A 1 4 binary inputs Case X000 Optional communication module See technical manual for details about different type of communication...

Page 18: ...02 8D43 D912D5EF0360 V1 EN Figure 2 Example of the LHMI 2 4 1 Display The LHMI includes a graphical display that supports two character sizes The character size depends on the selected language The am...

Page 19: ...of the LHMI The LEDs can be configured with the LHMI WHMI or PCM600 2 4 3 Keypad The LHMI keypad contains push buttons which are used to navigate in different views or menus With the push buttons you...

Page 20: ...o take a secured HTTPS connection to WHMI using TLS encryption The WHMI is verified with Internet Explorer 8 0 9 0 10 0 and 11 0 WHMI is enabled by default WHMI offers several functions Programmable L...

Page 21: ...and buttons Command buttons can be used to edit parameters and control information via the WHMI Table 5 Command buttons Name Description Enabling parameter editing Disabling parameter editing Writing...

Page 22: ...cord files Viewing all fault records Clearing all fault records Importing settings Exporting settings Selecting all Clearing all selections Refreshing the parameter list view 2 6 Authorization Four us...

Page 23: ...reconstruction and examination of the sequence of system and security related events and changes in the protection relay Both audit trail events and process related events can be examined and analyze...

Page 24: ...61850 8 1 MMS WHMI FTP or LHMI Logout Successful logout from IEC 61850 8 1 MMS WHMI FTP or LHMI Password change Password changed Firmware reset Reset issued by user or tool Audit overflow Too many aud...

Page 25: ...EC 61850 and Modbus Operational information and controls are available through these protocols However some communication functionality for example horizontal communication between the protection rela...

Page 26: ...ion of self healing loop topology it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches Otherwise connecting the loop topology can...

Page 27: ...station communication It is based on two complementary protocols defined in the IEC 62439 3 2012 standard parallel redundancy protocol PRP and high availability seamless redundancy HSR protocol Both p...

Page 28: ...SANs are either attached to one network only and can therefore communicate only with DANs and SANs attached to the same network or are attached through a redundancy box a device that behaves like a D...

Page 29: ...a redundancy box that acts as a ring element For example a 615 or 620 series protection relay with HSR support can be used as a redundancy box IEC 61850 HSR Ethernet switch Redundancy box Redundancy...

Page 30: ...24...

Page 31: ...ult protection low stage EFLPTOC 11 Non directional earth fault protection high stage EFHPTOC 11 Circuit breaker failure protection CCBRBRF 1 Master trip TRPPTRC 2 High impedance differential protecti...

Page 32: ...group SELGAPC Each switch group has several instances Connections of binary inputs to functions GOOSE signals to functions functions to functions functions to binary outputs and functions to LEDs hav...

Page 33: ...ic is routed to switch group output GUID 1EFA82D5 F9E7 4322 87C2 CDADD29823BD V1 EN Figure 10 Output switch group OSWGAPC 3 2 3 Selector switch group SELGAPC The selector switch group SELGAPC has a nu...

Page 34: ...GUID E3AEC7AB 2978 402D 8A80 C5DE9FED67DF V1 EN Figure 11 Selector switch group SELGAPC Section 3 1MRS757455 E REB611 standardized configuration 28 REB611 Application Manual...

Page 35: ...n the CT connector when plug in unit is detached 1 X120 1 2 3 4 5 6 7 8 9 10 11 12 14 Io IL1 IL2 BI 4 BI 3 BI 2 BI 1 IL3 1 5A N 1 5A N 1 5A N 1 5A N 13 L1 L2 L3 N Ru Ru Ru Rs Rs Rs GUID 72C26156 5904...

Page 36: ...or when plug in unit is detached 1 X120 1 2 3 4 5 6 7 8 9 10 11 12 14 Io IL1 IL2 BI 4 BI 3 BI 2 BI 1 IL3 1 5A N 1 5A N 1 5A N 1 5A N 13 3 Ru Rs Ru Ru Rs G Rs GUID 000FA2D5 6D6C 4A66 9772 7741A0BA3E91...

Page 37: ...nd non directional earth fault protection is mainly intended for use in high impedance basedapplicationswithin utilitysubstationsandindustrialpowersystems Inaddition the protection relay can also be u...

Page 38: ...OR 3 Io Uo Calculated value CONDITION MONITORING AND SUPERVISION CONTROL AND INDICATION 1 MEASUREMENT 3I Io Limit value supervision Symmetrical components BUSBAR AND MULTIPURPOSE DIFFERENTIAL PROTECTI...

Page 39: ...PO4 Open trip coil 2 X100 20 24 X100 SO1 General start indication X100 10 12 X100 SO2 General operate indication X100 13 15 Table 13 Default connections for LEDs LED Description 1 High impedance diff...

Page 40: ...log channels available for the disturbance recorder function These channels are freely selectable and a part of the disturbance recorder s parameter settings 3 4 3 1 Functional diagrams for protection...

Page 41: ...are connected to LED 4 HZCCCSPVC1 MCS 1I 3 MCS 1I 3 BLOCK ALARM I_C HZCCBSPVC1 MCS 1I 2 MCS 1I 2 BLOCK ALARM I_B HZCCASPVC1 MCS 1I 1 MCS 1I 1 BLOCK ALARM I_A LED 5 SELGAPC4 OUT_5 IN_13 OSWGAPC11 OR O...

Page 42: ...DIF1_OPERATE EFHPTOC1_OPERATE 51BF 51NBF 1 3I I0 START TRRET TRBU POSCLOSE CB_FAULT BLOCK CB_FAULT_AL CCBRBRF1 3I I0 BF 1 GUID 03078895 719E 4704 84A7 EDFFBE60DD4A V2 EN Figure 19 Circuit breaker fail...

Page 43: ...ternatively only to be recorded by the disturbance recorder depending on the parameter settings Additionally the selected autoreclosing output signals and the three binary inputs from X120 are also co...

Page 44: ...5_ACT 4 level trigger off Binary channel 22 SG_6_ACT 4 level trigger off X120 BI3 OR LED 7 TRIP CIRCUIT SUPERVISION SELGAPC1 OUT_3 IN_3 TRPPTRC1_TRIP TRPPTRC2_TRIP TCSSCBR1 BLOCK ALARM TCSSCBR2 BLOCK...

Page 45: ...1 Q2 IN1 IN2 MVGAPC1 OR GOOSERCV_BIN 2_OUT GOOSERCV_BIN 3_OUT GUID AFCBCEC5 678B 4F8B 9963 FFE91A7F1233 V3 EN Figure 22 Master trip The operate signals from the protections and an external trip are co...

Page 46: ...ing An always true signal is also connected to ENA_CLOSE via SELGAPC1 by default The open operation is always enabled X100 SO1 X100 SO2 COMMON ALARM INDICATION 1 2 SELGAPC3 OUT_3 IN_5 OUT_4 IN_9 TPGAP...

Page 47: ...EFLPTOC1 EFHPTOC1 HZCCASPVC1 HZCCBSPVC1 HZCCCSPVC1 CBXCBR1 TCSSCBR1 TCSSCBR2 CCBRBRF1 ISWGAPC1 SELGAPC2 Blocking TCS Blocking ISWGAPC9 GOOSE Blocking ISWGAPC10 GOOSE Block CB Alarm Trip Start Master t...

Page 48: ...Always True OUT_1 OUT_2 OUT_3 OUT_4 OUT_5 OUT_6 OUT_7 OUT_8 OUT_9 CBXCBR1_ENA_CLOSE TRPTTRC1_RST_LKOUT TRPTTRC2_RST_LKOUT TRPTTRC1 2_ RST_LKOUT CB Close Enable CBXCBR1_POSCLOSE SELGAPC2_IN_1 GUID C41...

Page 49: ...OUT_1 connection IN_1 If X100 PO4 is used for closing the circuit breaker TCSSCBR2 needs to be blocked by the circuit breaker close position OUT_2 connection IN_1 SELGAPC2 IN_1 IN_2 OUT_1 OUT_2 TCSSCB...

Page 50: ...C11 Alarm 1 TRPPTRC1 TPGAPC3 TPGAPC4 TPGAPC5 TPGAPC6 SELGAPC3 HIAPDIF1_OPERATE HIBPDIF1_OPERATE HICPDIF1_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE CCBRBRF1_TRRET HIAPDIF1_START HIBPDIF1_START HICPDIF1...

Page 51: ...CCBRBRF1_TRRET HIAPDIF1_START HIBPDIF1_START HICPDIF1_START EFLPTOC1_START EFHPTOC1_START HIAPDIF1_OPERATE HIBPDIF1_OPERATE HICPDIF1_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE Master Trip 1 OSWGAPC1 T...

Page 52: ...Backup Trip CBXCBR_EXE_OP TRPPTRC1_TRIP TRPPTRC2_TRIP CCBRBRF1_TRBU CB Open 1 CB Close TPGAPC1 IN1 OUT1 IN2 OUT2 TPGAPC7 IN1 OUT1 IN2 OUT2 TPGAPC6 IN1 OUT1 IN2 OUT2 TPGAPC5 IN1 OUT1 IN2 OUT2 TPGAPC4 I...

Page 53: ...C8_OUT OSWGAPC9_OUT OSWGAPC10_OUT OSWGAPC3_OUT OSWGAPC4_OUT CCBRBRF1_TRBU Backup Trip CB Close CB Open 1 CBXCBR_EXE_OP TRPPTRC1_TRIP CBXCBR_EXE_CL TRPPTRC2_TRIP CB Open 2 GUID ACEEEFCD 3CA8 4157 BD3E...

Page 54: ...2 GUID 58E5C510 F4F4 48A6 A334 C463F463FAB5 V2 EN Figure 36 OSWGAPC2 Start OSWGAPCs OSWGAPC instances 3 6 are used to configure the protection start signals These four OSWGAPCs have the same inputs fr...

Page 55: ...Figure 39 OSWGAPC5 Start 4 TPGAPC2_IN2 SELGAPC4_IN_8 OSWGAPC6 IN_1 IN_2 IN_3 IN_4 IN_5 OUT EFHPTOC1_START HIAPDIF1_START EFLPTOC1_START HICPDIF1_START HIBPDIF1_START GUID C924A4BA AC97 420E B676 C8C1...

Page 56: ...OUT EFHPTOC1_OPERATE HIAPDIF1_OPERATE EFLPTOC1_OPERATE HICPDIF1_OPERATE HIBPDIF1_OPERATE GUID 4FC22392 CF64 4B6E B015 A41720B2155F V2 EN Figure 42 OSWGAPC8 Trip 3 TPGAPC4_IN1 SELGAPC4_IN_11 OSWGAPC9 I...

Page 57: ...have the same inputs from the alarm signals The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4 directly Alarm 1 TPGAPC5_IN1 SELGAPC4_IN_13 OSWGAPC11 IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7...

Page 58: ...25 B0E0 4F04 8497 79F61F419523 V2 EN Figure 46 OSWGAPC12 Alarm 3 TPGAPC6_IN1 SELGAPC4_IN_15 OSWGAPC13 IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 IN_9 IN_10 IN_11 OUT TCSSCBR1_ALARM TRPPTRC1_CL_LKOUT TRPP...

Page 59: ...79 58B4 4C96 8B31 5560C6EC5D53 V2 EN Figure 48 OSWGAPC14 Alarm 5 TPGAPC7_IN1 SELGAPC4_IN_17 OSWGAPC15 IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 IN_9 IN_10 IN_11 OUT TCSSCBR1_ALARM TRPPTRC1_CL_LKOUT TRPP...

Page 60: ...can be configured in PCM600 GOOSERCV_BIN instances 0 and 1 are used for blocking protection functions Signals from these two GOOSERCV_BINs are connected to ISWGAPC9 ISWGAPC9 is used to configure which...

Page 61: ...SWGAPC9 ISWGAPC9 is used to configure which protection functions can be blocked by the received GOOSE signals ISWGAPC9 inputs are received GOOSE signals from GOOSERCV_BIN 0 and GOOSERCV_BIN 1 The outp...

Page 62: ...outputs are connected to block the circuit breaker close and open operation ISWGAPC10 IN OUT_1 OUT_2 CBXCBR1_BLK_CLOSE CBXCBR1_BLK_OPEN GOOSERCV_BIN 4_OUT GOOSERCV_BIN 5_OUT GOOSERCV_BIN 6_OUT GOOSER...

Page 63: ...s that is they have an equal burden and characteristics and are of the same type preferably from the same manufacturing batch If the CT characteristics and burden values are not equal calculations for...

Page 64: ...easuring branch during the out of zone fault is calculated assuming that one of the CTs connected in parallel is fully saturated The stabilizing voltage can be calculated using the formula U I n R R s...

Page 65: ...s s rs GUID EA4FE2BC 4E93 4093 BD14 F20A4F33AEF2 V1 EN Equation 3 Rs the resistance of the stabilizing resistor Us the stabilizing voltage of the protection relay Irs the value of the Operate value s...

Page 66: ...te value for Equation 5 The selection of current transformers can be divided into procedures 1 The rated current In of the feeder should be known The value of In also affects how high Ikmax is 2 The r...

Page 67: ...studied case by case If Ukn 1 5 Us the protection relay operation is jeopardized Another CT has to be chosen The need for the VDR depends on certain conditions First voltage Umax ignoring the CT satur...

Page 68: ...V1 EN Equation 10 As the peak voltage is 3 2 kV VDR must be used If the Rsis smaller VDR could be avoided However the value of Rs depends on the operation current and stabilizing voltage of the prote...

Page 69: ...0 IL2 X120 11 12 IL3 5 1 1 2 Residual current Table 17 Residual current input included in configuration A Terminal Description X120 13 14 Io 5 1 2 Auxiliary supply voltage input The auxiliary voltage...

Page 70: ...ng and controlling Output contacts PO1 PO2 PO3 and PO4 are heavy duty trip contacts capable of controlling most circuit breakers In the factory default configuration the trip signals from all the prot...

Page 71: ...3 IRF The IRF contact functions as an output contact for the self supervision system of the protection relay Under normal operating conditions the protection relay is energized and the contact is clo...

Page 72: ...66...

Page 73: ...ble point control EMC Electromagnetic compatibility Ethernet A standard for connecting a family of frame based computer networking technologies into a LAN FIFO First in first out FTP File transfer pro...

Page 74: ...ation protocol developed by the Modicon company in 1979 Originally used for communication in PLCs and RTU devices PCM600 Protection and Control IED Manager PO Power output PRP Parallel redundancy prot...

Page 75: ...69...

Page 76: ...BB Distribution Solutions Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 www abb com mediumvoltage www abb com relion Copyright 2019 ABB All rights reserved 1MRS757455 E...

Reviews: