5.5
Connecting binary signals
Connect the wires for the binary signals to the correct device according to the
connection diagram. Each terminal for binary input and output signal is
dimensioned for one 0.5...2.5 mm
2
wire or for two 0.5...1.0 mm
2
wires.
See the specific card variant from the application manual.
GUID-1BE0210A-D182-4354-916E-EBEAF8F2BD48 V1 EN
Figure 50:
Example of BIO0005 card variant (8 BI + 4 BO)
1MRS756375 K
Section 5
Connecting
615 series
59