A070868-ANSI V1 EN
Figure 508:
Signal scheme of autoreclosing operation initiated with protection trip
signal
The autoreclosing shot is initiated with a trip signal of the protection function. The
autoreclosing picks up when the protection trip delay time elapses.
Normally, all trip and pickup signals are used to initiate an autoreclosing shot and trip the
circuit breaker.
ACTIVE
output indicates reclosing sequence in progress. If any of the
input signals
INIT_X
or
DEL_INIT_X
are used for blocking, the corresponding bit in
the
Tripping line
setting must be FALSE. This is to ensure that the circuit breaker does not
trip from that signal, that is, the signal does not activate the
OPEN_CB
output. The default
value for the setting is "63", which means that all initiation signals activate the
OPEN_CB
output. The lowest bit in the
Tripping line
setting corresponds to the
INIT_1
input, the
highest bit to the
INIT_6
line.
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
999
Technical Manual