Figure 514:
Initiation after elapsed discrimination time - new shot begins
9.4.4.5
Sequence controller
When the
LOCKED
output is active, the AR function is in lockout. This means that new
sequences cannot be initialized, because AR is insensitive to initiation commands. It can
be released from the lockout state in the following ways.
•
The function is reset through communication with the
RecRs
parameter. The same
functionality can also be found in the Clear menu (79 reset).
•
The lockout is automatically reset after the reclaim time, if the
Auto lockout reset
setting is in use.
If the
Auto lockout reset
setting is not in use, the lockout can be released
only with the
RecRs
parameter.
The AR function can go to lockout for many reasons.
•
The
INHIBIT_RECL
input is active.
•
All shots have been executed and a new initiation is made (final trip).
•
The time set with the
Auto wait time
parameter expires and the automatic sequence
initiation is not allowed because of a synchronization failure.
•
The time set with the
Wait close time
parameter expires, that is, the circuit breaker
does not close or the automatic sequence initiation is not allowed due to a closing
failure of the circuit breaker.
•
A new shot is initiated during the discrimination time.
•
The time set with the
Max wait time
parameter expires, that is, the master unit does
not release the slave unit.
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
1007
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......