Example 1
When a two-shot-sequence is used, the pickup information from the protection function is
routed to the
DEL_INIT 2
input and the trip information to the
INIT_2
input. The
following conditions have to apply:
•
protection trip time = 0.5s
•
Str 2 delay shot 1
= 0.05s
•
Str 2 delay shot 2
= 60s
•
Str 2 delay shot 3
= 60s
Operation in a permanent fault:
1. Protection picks up and activates the
DEL_INIT 2
input.
2. After 0.05 seconds, the first autoreclose shot is initiated. The function opens the
circuit breaker: the
OPEN_CB
output activates. The total trip time is the protection
pickup delay + 0.05 s the time it takes to open the circuit breaker.
3. After the first shot, the circuit breaker is reclosed and the protection picks up again.
4. Because the delay of the second shot is 60 seconds, the protection is faster and trips
after the set operation time, activating the
INIT 2
input. The second shot is initiated.
5. After the second shot, the circuit breaker is reclosed and the protection picks up again.
6. Because the delay of the second shot is 60 seconds, the protection is faster and trips
after the set operation time. No further shots are programmed after the final trip. The
function is in lockout and the sequence is considered unsuccessful.
Example 2
The delays can be used also for fast final trip. The conditions are the same as in Example
1, with the exception of
Str 2 delay shot 3
= 0.10 seconds.
The operation in a permanent fault is the same as in Example 1, except that after the second
shot when the protection picks up again,
Str 2 delay shot 3
elapses before the protection
trip time and the final trip follows. The total trip time is the protection pickup delay + 0.10
s the time it takes to open the circuit breaker.
9.4.6.6
Fast trip in Switch on to fault
The
Str _ delay shot 4
parameter delays can also be used to achieve a fast and accelerated
trip with SOTF. This is done by setting the
Fourth delay in SOTF
parameter to "1" and
connecting the protection pickup information to the corresponding
DEL_INIT_
input.
When the function detects a closing of the circuit breaker, that is, any other closing except
the reclosing done by the function itself, it always prohibits shot initiation for the time set
with the
Reclaim time
parameter. Furthermore, if the
Fourth delay in SOTF
parameter is
"1", the
Str _ delay shot 4
parameter delays are also activated.
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
1025
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......