10.2.5
Application
PQVPH provides a method for monitoring the power quality by means of the voltage
waveform distortion. PQVPH provides a short-term three-second average and long-term
demand for THD.
10.2.6
Signals
Table 921:
PQVPH Input signals
Name
Type
Default
Description
V_A_AB
SIGNAL
0
Phase A voltage
V_B_BC
SIGNAL
0
Phase B voltage
V_C_CA
SIGNAL
0
Phase C voltage
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 922:
PQVPH Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm signal for THD
10.2.7
Settings
Table 923:
PQVPH Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Demand interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
2=10 minutes
Time interval for demand calculation
Demand window
1=Sliding
2=Non-sliding
1=Sliding
Demand calculation window type
THD alarm limit
1.0...100.0
%
0.1
50.0
THD alarm limit
1MAC059074-MB A
Section 10
Power quality measurement functions
615 series ANSI
1039
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......