activate the
PICKUP
output and the corresponding phase output, that is, all the monitored
phases have to be activated. Accordingly, the deactivation occurs when the activation
requirement is not fulfilled, that is, one or more monitored phase signal magnitudes return
beyond their limits. Phases do not need to be activated by the same variation type to
activate the
PICKUP
output. Another consequence is that if only one or two phases are
monitored, it is sufficient that these monitored phases activate the
PICKUP
output.
10.3.4.2
Variation detection
The module compares the measured voltage against the limit settings. If there is a
permanent undervoltage or overvoltage, the
Reference voltage
setting can be set to this
voltage level to avoid the undesired voltage dip or swell indications. This is accomplished
by converting the variation limits with the
Reference voltage
setting in the variation
detection module, that is, when there is a voltage different from the nominal voltage, the
Reference voltage
setting is set to this voltage.
The
Variation enable
setting is used for enabling or disabling the variation types. By
default, the setting value is "Swell+dip+Int" and all the alternative variation types are
indicated. For example, for setting "Swell+dip", the interruption detection is not active
and only swell or dip events are indicated.
In a case where
Phase mode
is "Single Phase" and the dip functionality is available, the
output
DIPST
is activated when the measured TRMS value drops below the
Voltage dip
set 3
setting in one phase and also remains above the
Voltage Int set
setting. If the voltage
drops below the
Voltage Int set
setting, the output
INTST
is activated.
INTST
is
deactivated when the voltage value rises above the setting
Voltage Int set
. When the same
measured TRMS magnitude rises above the setting
Voltage swell set 3
, the
SWELLST
output is activated.
There are three setting value limits for dip (
Voltage dip set 1..3
) and swell activation
(
Voltage swell set 1..3
) and one setting value limit for interruption.
If
Phase mode
is "Three Phase", the
DIPST
and
INTST
outputs are
activated when the voltage levels of all monitored phases, defined with the
parameter
Phase supervision
, drop below the
Voltage Int set
setting value.
An example for the detection principle of voltage interruption for "Three
Phase" when
Phase supervision
is "Ph A + B + C", and also the
corresponding pickup signals when
Phase mode
is "Single Phase", are as
shown in the example for the detection of a three-phase interruption.
1MAC059074-MB A
Section 10
Power quality measurement functions
615 series ANSI
1043
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......