Table 936:
Trigger mode observation times
Trigger mode
Observation time
Single
Only one period of observation time is activated.
Periodic
The time gap between the two trigger signals is
seven days.
Continuous
The next period starts right after the previous
observation period is completed.
The length of the period is determined by the settings
Obs period selection
and
User Def
Obs period
. The
OBS_PR_ACT
output is an indication signal which exhibits rising edge
(TRUE) when the observation period starts and falling edge (FALSE) when the
observation period ends.
If the
Percentile unbalance
,
Trigger mode
or
Obs period duration
settings change when
OBS_PR_ACT
is active,
OBS_PR_ACT
deactivates immediately.
1MAC059074-MB A
Section 10
Power quality measurement functions
615 series ANSI
1065
Technical Manual