The delayed inverse-time reset is not available for IEC-type inverse time
curves.
User-programmable delayed inverse reset
The user can define the delayed inverse reset time characteristics with the following
formula using the set
Curve parameter D
.
t s
D
I
I
k
[ ]
=
>
−
⋅
2
1
A060817 V3 EN
(Equation 178)
t[s] Reset time (in seconds)
k
set
Time multiplier
D
set
Curve parameter D
I
Measured current
I>
set
Pickup value
11.2.3
Inverse-timer freezing
When the
BLOCK
input is active, the internal value of the time counter is frozen at the
value of the moment just before the freezing. Freezing of the counter value is chosen when
the user does not wish the counter value to count upwards or to be reset. This may be the
case, for example, when the inverse-time function of a protection relay needs to be
blocked to enable the definite-time operation of another protection relay for selectivity
reasons, especially if different relaying techniques (old and modern relays) are applied.
The selected blocking mode is "Freeze timer".
The activation of the
BLOCK
input also lengthens the minimum delay
value of the timer.
Section 11
1MAC059074-MB A
General function block features
1110
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......