Table 50:
Binary input states
Control voltage
Input # invert
State of binary input
No
0
FALSE (0)
Yes
0
TRUE (1)
No
1
TRUE (1)
Yes
1
FALSE (0)
When a binary input is inverted, the state of the input is TRUE (1) when no control voltage
is applied to its terminals. Accordingly, the input state is FALSE (0) when a control
voltage is applied to the terminals of the binary input.
3.11.3
Oscillation suppression
Oscillation suppression is used to reduce the load from the system when a binary input
starts oscillating. A binary input is regarded as oscillating if the number of valid state
changes (= number of events after filtering) during one second is equal to or greater than
the set oscillation level value. During oscillation, the binary input is blocked (the status is
invalid) and an event is generated. The state of the input will not change when it is blocked,
that is, its state depends on the condition before blocking.
The binary input is regarded as non-oscillating if the number of valid state changes during
one second is less than the set oscillation level value minus the set oscillation hysteresis
value. Note that the oscillation hysteresis must be set lower than the oscillation level to
enable the input to be restored from oscillation. When the input returns to a non-oscillating
state, the binary input is deblocked (the status is valid) and an event is generated.
Table 51:
Oscillation parameter values
Parameter
Values
Default
Input osc. level
2...50 events/s
30 events/s
Input osc. hyst
2...50 events/s
10 events/s
3.12
Binary outputs
The protection relay provides a number of binary outputs used for tripping, executing
local or remote control actions of a breaker or a disconnector, and for connecting the
protection relay to external annunciation equipment for indicating, signalling and
recording.
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
107
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......