Peak-to-peak with peak backup
The peak-to-peak with peak backup measurement principle is selected with the
Measurement mode
setting using the value "P-to-P+backup". It is similar to the peak-to-
peak mode, with the exception that it has been enhanced with the peak backup. In the peak-
to-peak with peak backup mode, the function starts with two conditions: the peak-to-peak
value is above the set pickup current or the peak value is above two times the set
Pickup
value
. The peak backup is enabled only when the function is used in the DT mode in high
and instantaneous stages for faster operation.
Wide peak-to-peak
The wide peak-to-peak measurement mode is available only in the three-phase
overcurrent protection function 51P in REG615 standard configurations C and D. The
wide peak-to-peak measurement principle is available in products where it is necessary
for overcurrent protection to operate already starting from as low frequency as 2 Hz during
the generator start-up or shutdown phase. The wide peak-to-peak measurement principle
is selected with the
Measurement mode
setting "Wide P-to-P".
The measurement mode calculates the average from the positive and negative peak values
over the 500 ms wide measurement window, independently of the
Frequency adaptivity
setting value. Retardation and reset times are longer due to the length of the measurement
window. The frequency of the fault current affects the operate time. The damping of the
harmonics is quite low and practically determined by the characteristics of the anti-
aliasing filter of the protection relay current inputs.
When using measurement mode “Wide P-to-P”, the protection relay
accepts only
Trip delay time
setting value 800 ms or longer and
Operating
curve type
5=”ANSI Def. Time” or 15=”IEC Def. Time”.
Operation accuracy in the frequency range 2...85 Hz is ±1.5% or ±0.003 × I
n
. Operate time
accuracy in definite time mode is ±1.0% of the set value or ±60 ms when I
Fault
= 2 × set
Pickup value
and the fault current frequency is 10...85 Hz.
11.7
Calculated measurements
Calculated residual current and voltage
The residual current is calculated from the phase currents according to equation:
Io
I
I
I
A
B
C
= −
+
+
(
)
GUID-B9280304-8AC0-40A5-8140-2F00C1F36A9E V1 EN
(Equation 184)
1MAC059074-MB A
Section 11
General function block features
615 series ANSI
1127
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......