Table 957:
2-wire EIA-485 jumper connectors
Group
Jumper connection
Description
Notes
X4
1-2
A+ bias enabled
COM2
2-wire connection
2-3
A+ bias disabled
X5
1-2
B- bias enabled
2-3
B- bias disabled
X6
1-2
Bus termination enabled
2-3
Bus termination disabled
X7
1-2
B- bias enabled
COM1
2-wire connection
2-3
B- bias disabled
X8
1-2
A+ bias enabled
2-3
A+ bias disabled
X9
1-2
Bus termination enabled
2-3
Bus termination disabled
The bus is to be biased at one end to ensure fail-safe operation, which can be done using
the pull-up and pull-down resistors on the communication module. In 4-wire connection
the pull-up and pull-down resistors are selected by setting jumpers X4, X5, X7 and X8 to
enabled position. The bus termination is selected by setting jumpers X6 and X9 to enabled
position.
The jumpers have been set to no termination and no biasing as default.
Table 958:
4-wire EIA-485 jumper connectors for COM2
Group
Jumper connection
Description
Notes
X4
1-2
A+ bias enabled
COM2
4-wire TX channel
2-3
A+ bias disabled
1)
X5
1-2
B- bias enabled
2-3
B- bias disabled
1)
X6
1-2
Bus termination enabled
2-3
Bus termination
disabled
1)
X7
1-2
B- bias enabled
COM2
4-wire RX channel
2-3
B- bias disabled
1)
X8
1-2
A+ bias enabled
2-3
A+ bias disabled
1)
X9
1-2
Bus termination enabled
2-3
Bus termination
disabled
1)
1) Default setting
Section 13
1MAC059074-MB A
Protection relay's physical connections
1152
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......