Description
Value
Logic level
5 V TTL
Current consumption
<4 mA
Power consumption
<20 mW
1) According to the 200-04 IRIG standard
Table 992:
Lens sensor and optical fiber for arc protection
Description
Value
Fiber optic cable including lens
1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens
-40...+100°C
Maximum service temperature range of the lens,
max 1 h
+140°C
Minimum permissible bending radius of the
connection fiber
3.94 inches (100 mm)
Table 993:
Degree of protection of flush-mounted protection relay
Description
Value
Front side
IP 54
Rear side, connection terminals
IP 10
Left and right side
IP 20
Top and bottom
IP 20
Table 994:
Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
•
REF615, REG615, REM615 and RET615:
-40...+85ºC (<16 h)
1)2)
•
RED615: -40...+70ºC (<16 h)
1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
12.47...15.37 psi (86...106 kPa)
Altitude
Up to 6561.66 feet (2000 m)
Transport and storage temperature range
-40...+85ºC
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For relays with an LC communication interface the maximum operating temperature is +70 ºC
1MAC059074-MB A
Section 14
Technical data
615 series ANSI
1173
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......