Description
Type test value
Reference
Power frequency (50 Hz)
magnetic field immunity test
IEC 61000-4-8
•
Continuous
•
1...3 s
300 A/m
1000 A/m
Pulse magnetic field immunity test 1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field
immunity test
IEC 61000-4-10
•
2 s
100 A/m
•
1 MHz
400 transients/s
Voltage dips and short
interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Power frequency immunity test
Binary inputs only
IEC 61000-4-16
IEC 60255-26, class A
•
Common mode
300 V rms
•
Differential mode
150 V rms
Conducted common mode
disturbances
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Emission tests
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
•
Conducted
0.15...0.50 MHz
<79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz
<73 dB (µV) quasi peak
<60 dB (µV) average
•
Radiated
30...230 MHz
<40 dB (µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz
<47 dB (µV/m) quasi peak,
measured at 10 m distance
1…3 GHz
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
3…6 GHz
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
Section 15
1MAC059074-MB A
Protection relay and functionality tests
1176
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......