3.13.2.3
Input linear scaling
Each RTD/mA input can be scaled linearly by the construction of a linear output function
in respect to the input. The curve consists of two points, where the y-axis (
Input minimum
and
Input maximum
) defines the input range and the x-axis (
Value minimum
and
Value
maximum
) is the range of the scaled value of the input.
The input scaling can be bypassed by selecting
Value unit
= "Ohm" when
Input mode
= "Resistance" is used and by selecting
Value unit
= "Ampere"
when
Input mode
= "0...20 mA" is used.
Example for linear scaling
Milliampere input is used as tap changer position information. The sensor information is
from 4 mA to 20 mA that is equivalent to the tap changer position from -36 to 36,
respectively.
Input maximum
Input minimum
Input mode
”0..20mA”
4 mA
20 mA
Value minimum
-36
AI_VAL#
Value maximum
36
Value unit
”Dimensionless”
X130-Input#
GUID-85338A5E-3D2F-4031-A598-EA8A525190D3 V1 EN
Figure 30:
Milliampere input scaled to tap changer position information
3.13.2.4
Measurement chain supervision
Each input contains a functionality to monitor the input measurement chain. The circuitry
monitors the RTD channels continuously and reports a circuitry break of any enabled
input channel. If the measured input value is outside the limits, minimum/maximum value
is shown in the corresponding output. The quality of the corresponding output is set
accordingly to indicate misbehavior in the RTD/mA input.
Section 3
1MAC059074-MB A
Basic functions
116
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......