Table 146:
62TPS Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
Table 147:
62TPS Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Cold load time
0...300
s
1
0
Cold load time
Technical revision history
Table 148:
67TPS Technical revision history
Technical revision
Change
B
Outputs now visible in menu
C
Internal improvement
3.17.2.3
Minimum pulse timer 62TPM
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum minute pulse timer (2 pcs)
TPMGAPC
TPM
62TPM
Function block
62TPM
OUT2
OUT1
IN1
IN2
GUID-4B1768D1-AC32-4305-893F-9CEEFEA24AC8 V1 EN
Figure 80:
Function block
Functionality
The Minimum minute pulse timer function 62TPM contains two independent timers. The
function has a settable pulse length (in minutes). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated, the
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
167
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......