3.17.10
Local/remote control function block CONTROL
3.17.10.1
Function block
GUID-FA386432-3AEF-468D-B25E-D1C5BDA838E3 V3 EN
Figure 92:
Function block
3.17.10.2
Functionality
Local/Remote control is by default realized through the R/L button on the front panel. The
control via binary input can be enabled by setting the value of the
LR control
setting to
"Binary input". The binary input control requires that the CONTROL function is
instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in substations
according to the IEC 61850 standard. Multilevel control access with separate station
control access level is not supported by other protocols than IEC 61850.
The actual Local/Remote control state is evaluated by the priority scheme on the function
block inputs. If more than one input is active, the input with the highest priority is selected.
The priority order is “off”, “local”, “station”, “remote”, “all”.
The actual state is reflected on the CONTROL function outputs. Only one output is active
at a time.
Table 176:
Truth table for CONTROL
Input
Output
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
TRUE
N/A
N/A
N/A
N/A
OFF = TRUE
FALSE
TRUE
N/A
N/A
N/A
LOCAL =
TRUE
FALSE
FALSE
TRUE
N/A
N/A
STATION =
TRUE
FALSE
FALSE
FALSE
TRUE
TRUE
REMOTE =
TRUE
FALSE
FALSE
FALSE
FALSE
TRUE
ALL = TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
OFF = TRUE
Section 3
1MAC059074-MB A
Basic functions
182
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......