Figure 95:
Station authority is “L,S,R”
When the station authority level “L,S,R” is used, the control access can be selected using
R/L button or CONTROL function block. IEC 61850 data object CTRL.LLN0.LocSta
and CONTROL function block input
CTRL_STA
are applicable for this station authority
level.
Station control access can be reserved by using R/L button or CONTROL function block
together with IEC 61850 data object CTRL.LLN0.LocSta.
Table 181:
Station authority level “L,S,R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850
client
2)
IEC 61850
client
3)
Local
FALSE
FALSE
1
x
Remote
FALSE
FALSE
2
x
Remote
TRUE
FALSE
3
x
Off
FALSE
FALSE
0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
Section 3
1MAC059074-MB A
Basic functions
186
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......