3.20.1.3
Signals
Table 201:
RCHLCCH output signals
Parameter
Values (Range) Unit
Step
Default
Description
CHLIV
True
False
Status of redundant Ethernet channel
LAN A. When
Redundant mode is set to
"HSR" or "PRP", value is "True" if the
protection relay is receiving redundancy
supervision frames. Otherwise value is
"False".
REDCHLIV
True
False
Status of redundant Ethernet channel
LAN B. When
Redundant mode is set to
"HSR" or "PRP", value is "True" if the
protection relay is receiving redundancy
supervision frames. Otherwise value is
"False".
LNKLIV
Up
Down
Link status of redundant port LAN A. Valid
only when
Redundant mode is set to
"HSR" or "PRP".
REDLNKLIV
Up
Down
Link status of redundant port LAN B. Valid
only when
Redundant mode is set to
"HSR" or "PRP".
3.20.1.4
Settings
Table 202:
Redundancy settings
Parameter
Values (Range) Unit
Step
Default Description
Redundant
mode
None
PRP
HSR
None
Mode selection for Ethernet switch on
redundant communication modules. The
"None" mode is used with normal and Self-
healing Ethernet topologies.
3.20.1.5
Monitored data
Monitored data is available in four locations.
•
Monitoring/Communication/Ethernet/Activity/CHLIV_A
•
Monitoring/Communication/Ethernet/Activity/REDCHLIV_B
•
Monitoring/Communication/Ethernet/Link statuses/LNKLIV_A
•
Monitoring/Communication/Ethernet/Link statuses/REDLNKLIV_B
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
207
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......