The
Characteristic angle
setting is used to turn the directional characteristic. The value of
Characteristic angle
should be chosen in such a way that all the faults in the operating
direction are seen in the operating zone and all the faults in the opposite direction are seen
in the non-operating zone. The value of
Characteristic angle
depends on the network
configuration.
Reliable operation requires both the operating and polarizing quantities to exceed certain
minimum amplitude levels. The minimum amplitude level for the operating quantity
(current) is set with the
Min trip current
setting. The minimum amplitude level for the
polarizing quantity (voltage) is set with the
Min trip voltage
setting. If the amplitude level
of the operating quantity or polarizing quantity is below the set level, the direction
information of the corresponding phase is set to "Unknown".
The polarizing quantity validity can remain valid even if the amplitude of the polarizing
quantity falls below the value of the
Min trip voltage
setting. In this case, the directional
information is provided by a special memory function for a time defined with the
Voltage
Mem time
setting.
67/51P, 67/50P is provided with a memory function to secure a reliable and correct
directional protection relay operation in case of a close short circuit or a ground fault
characterized by an extremely low voltage. At sudden loss of the polarization quantity, the
angle difference is calculated on the basis of a fictive voltage. The fictive voltage is
calculated using the positive phase sequence voltage measured before the fault occurred,
assuming that the voltage is not affected by the fault. The memory function enables the
function to trip up to a maximum of three seconds after a total loss of voltage. This time
can be set with the
Voltage Mem time
setting. The voltage memory cannot be used for the
"Negative sequence voltage" polarization because it is not possible to substitute the
positive sequence voltage for negative sequence voltage without knowing the network
unsymmetry level. This is the reason why the fictive voltage angle and corresponding
direction information are frozen immediately for this polarization mode when the need for
a voltage memory arises and these are kept frozen until the time set with
Voltage Mem time
elapses.
The value for the
Min trip voltage
setting should be carefully selected
since the accuracy in low signal levels is strongly affected by the
measuring device accuracy.
When the voltage falls below
Min trip voltage
at a close fault, the fictive voltage is used
to determine the phase angle. The measured voltage is applied again as soon as the voltage
rises above
Min trip voltage
and hysteresis. The fictive voltage is also discarded if the
measured voltage stays below
Min trip voltage
and hysteresis for longer than
Voltage Mem
time
or if the fault current disappears while the fictive voltage is in use. When the voltage
is below
Min trip voltage
and hysteresis and the fictive voltage is unusable, the fault
direction cannot be determined. The fictive voltage can be unusable for two reasons:
Section 4
1MAC059074-MB A
Protection functions
234
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......